Specifications
78
8.0
S
PECIFICATIONS
8.1
AC8 Specifications
Power
Requirements
Transformer Module
NOTE
115VAC
UML11500
230VAC
UML23000
If the equipment is
used in a manner
not specified by the
manufacturer, the
protection provided
by the equipment
may be impaired.
115VAC ±10%
of nominal;
60Hz, 4A,
460VA
230VAC ±10%
of nominal;
50Hz, 0.5A,
115VA
Dimensions
W x D x H, in. (mm)
18 x 2-3/4 x 18
(457.2 x 69.85 x 457.2)
Weight (Assembled)
20.56 lb. (9.33 kg)
Enclosure Type
NEMA 1
Liquid Crystal Display (LCD)
Four line, 20 character, backlit
Mounting Surface
Building Wall or Structural Member
Ambient Operating
Environment
32ºF to 104ºF (0ºC to 40ºC)
0% RH to 95% RH (non-condensing)
Processor Specifics
Model
Motorola XC68HC812A4
Clock speed
16MHz
Total RAM
256Kb
Total FLASH
4M
Total EEPROM
4K
A/D Resolution (Analog IN)
12 Bit
Modem Type Embedded
14.4K bps
Clock Type
Real-Time Clock
Clock battery backup type
Lithium Cell (non-replaceable)
Clock battery life
7 years, constant, no power
Modem battery backup type
Nickel Cadmium (replaceable)
Modem battery life
10 minutes at full load
Communications
Local Communications
RS232
Remote Communications
Modem (9600-N-8-1)
Supported pagers
Baud rate 9600 bps, Parity=None, Data bits=8, Stop bits=1
9600 E-7-1 supports TAPI protocol version 1.8
SiteScan Web
IGM Protocol, EIA422
Agency Listings
Transformer Module
115VAC
(TM115)
230VAC
(TM230)
UL
UL1012
UL1585
CSA
C22.2 No. 66 and
C22.2 No. 107.1
CE
Yes
FCC Compliance
N/A
Inputs & Outputs (Quantity)
Digital Inputs (8)
Dry Contact Closure 24VDC, 10 mA
Analog Inputs (4)
4-20 mA signal input with selectable
power source of 12VDC or 24VDC
Digital Outputs (8)
24VAC, 3A
Common Alarm Outputs (2)
24VAC, 3A