Setup Menu
99
A.6.4 Setup Zones
For details on this feature, see
7.6 - Setup System - Setup Zones
.
A.6.5 Setup Output
For details on this feature, see
7.7 - Setup System - Setup Outputs
.
Setup Zones
SETUP ZONES
Select zones and number
of devices in the zone
ZONES
# DEVICES
1=ZONE 1
4
2=ZONE 2
0
3=ZONE 3
0
4=ZONE 4
0
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU
SELECT A NUMBER:
># DEVICES IN ZONE 1
>[4]
>[
Setup Outputs
SETUP OUTPUTS
Setup output of device
Select output to edit
OUTPUT
DEFINITION
*******************************************
NO=NORMALLY OPENED
1=DEVICE_1
NO-OP-E-E
NC=NORMALLY CLOSED
2=DEVICE_2
NO-OP-E-E
3=DEVICE_3
NO-OP-E-E
OP=OPERATING/ON
4=DEVICE_4
NO-ST-E-E
ST=STANDBY MODE
5=DEVICE_5
NO-NU-E-E
NU=NOT USED
6=DEVICE_6
NO-NU-E-E
7=DEVICE_7
NO-NU-E-E
D=DISABLE DEVICE ON ALARM CONDITION
8=DEVICE_8
NO-NU-E-E
E=LEAVE DEVICE OPERATING ON ALARM CONDITION
9=RETURN TO SETUP MENU
0=RETURN TO MAIN MENU
D=DISABLE DEVICE IN EMERGENCY POWER OP
E=LEAVE DEVICE OPERATING (EMERGENCY POWER OP)
*******************************************
SELECT A NUMBER:1
>SET TO NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)
>[NO]
>[]
>DEVICE_1 TO OPERATING/ON(OP), STANDBY MODE(ST), NOT USED(NU)
>[OP]
>[]
>DEVICE_1 TO ENABLE(E) OR DISABLE(D) DEVICE ON ALARM
>[E]
>[]
>DEVICE_1 TO ENABLE(E) OR DISABLE(D) DEVICE IN EMERGENCY POWER OP
>[E]
>[
Summary of Contents for Autochangeover Controllers AC8
Page 1: ...SITE MONITORING AND SERVICES AC8 USER MANUAL ...
Page 2: ......
Page 8: ...vi ...
Page 127: ......