Installation Instructions: Control Link ACC Anti-Condensate Controller System
technical bulletin
3. In the Connected I/O screen, in a box labeled
ECT Devices
. Enter the number of ACC devices in the
CtrlLink ACC
number field.
4. Press
J
to return to the Network Setup menu, then select
-
Controller Setup
.
5. Locate the CtrlLink ACC units you added to the network list (press
8
and
7
to scroll through the list). The
default name for a Control Link ACC begins with a two-letter designator of the model type (
AC
for anti-con-
densate). If desired, enter a new name for each device in the
Name
field.
6. By default, each CtrlLink ACC in the network list has a board number of 0. To set the address and begin
communication, press
D
and select
-
Select Address
. In the list of MODBUS devices, choose the
address number corresponding to the Control Links ACC’s dip switch/jumper setting, and press
>
to
select it. If a network ID has already been selected, its name will be shown next to the network ID in this list.
If the network ID you are trying to assign has already been used, you must set the network ID dip switch/
jumper on this device to a different number that is not being used.
Figure 11 - Connected I/O Screen
Figure 12 - Controller Setup Screen