6.4
Number of messages, red LED and buzzer
Every message on the display in front of the UPS corresponds to a
number on the two 7-segments displays mounted on UPS logic board.
Every message causes a programmed effect on red-alarm LED and
buzzer on panel of UPS; they are, in ascending order of importance:
red LED may be OFF, BLINKING, CONTINUOUS sound of buzzer
may be OFF, SINGLE PULSE, INTERMITTENT, CONTINUOUS.
It is possible to change the default program using a feature of
communication system (see handbook).
Sr. No. MESSAGE
Sound
Led
01.
NORMAL OPERATION
Off
Off
02.
BYPASS SWITCH OPEN
Cont.
On
03.
OUTPUT SWITCH OPEN
Cont.
On
04.
RECT. SWITCH OPEN
Cont.
On
05.
BATT. SWITCH OPEN
Cont.
On
06.
MANUAL BYPASS CLOSED
Pulse
Blinking
07.
08.
09.
10.
BYP: ABSENT
Interm.
Blinking
11.
BYP: OVER VOLTAGE
Interm.
Blinking
12.
BYP: UNDER VOLTAGE
Interm
Blinking
13.
BYP: FREQUENCY ERROR
Interm
Blinking
14.
BYP: PHASE ROT. ERROR
Cont.
On
15.
BYP: SCR FAILURE
Cont.
On
16.
BYP: HARDWARE BLOCK
Pulse
Blinking
17.
BYP: OFF VIA DISPLAY
Pulse
Blinking
18.
LOAD ON BYPASS
Interm.
Blinking
19.
BYP: OVER TEMPERATURE
Cont.
On
20.
RECT: SOFTWARE BLOCK
Interm
Blinking
21.
RECT: OFF VIA DISPLAY
Pulse
Blinking
22.
RECT: HARDWARE BLOCK
Cont.
On
23.
RECT: CURRENT LIMIT
Interm.
Blinking
24.
RECT: OVER TEMPERATURE
Cont.
On
25.
RECT. FUSE FAIL
Cont.
On
26.
27.
28.
29.
30.
INV SOFTWARE BLOCK
Interm
Blinking
31.
INV. OFF VIA DISPLAY
Interm
Blinking
7400M - Series UPS User Manual