1. Open the Battery circuit breaker and the Rectifier input power
switch Q1.
The Module Mimic indicator (2) Load on Inverter will extinguish and
the Load on Bypass Indicator (3) will flash amber. The battery not
available indicator (4) will light amber and the battery bar graph
LED's will all extinguish.
The display window will show messages reflecting the actions taken
(i.e. load on Bypass: Battery Breaker open: Rect. breaker open: etc.).
2. Open the Output power switch Q4 and the bypass power switch
Q2.
All operator LED indications and messages will extinguish as the
mains driven internal power supplies decay.
3. To completely isolate the UPS from the AC supplies, the main
external power Input isolator (both isolators, where separate supplies
are provided for rectifier and bypass) should be opened.
Wait 5 minutes for the internal DC bus bar capacitors to discharge.
The UPS Is now completely powered down.
IMPORTANT
The Maintenance Bypass Power switch may be operated at
any time when the UPS Is powered down to connect the load
to the maintenance bypass supply it required. The load
equipment is not protected from normal supply aberrations
when operating In the maintenance bypass mode.
7400M - Series UPS User Manual
Single Module and 1+N Parallel System