02/02
22
If the voltage indicated is satisfactory (432V DC for 380V AC system
446V DC for 400V DC system and 459V DC for 415 V AC system)
press the ESC key repeatedly until the display returns to the original
window.
6. Manually close the battery circuit breaker. This is located inside
the battery cabinet (if used) or otherwise located adjacent to the
battery racks.
The
Module Mimic
indicator (4)
Battery unavailable
should
extinguish. Several LED's on the
Battery state of charge bargraph
will
illuminate showing the battery state of charge.
When the battery circuit breaker has been closed and the inverter has
stabilized the screen will change to the default window.
Default Window. The message shown below, will be seen on the
default screen whenever the UPS is operating normally
The top lines display the UPS operational status and indicates alarm
conditions when they occur; and line tour normally shows the time
and date
The UPS is operating normally with its Inverter
supplying the load.
2.3
Procedure for Switching the UPS into a Maintenance Bypass condition from
normal operation.
This procedure should be followed to transfer the load from the UPS
inverter output to the maintenance bypass system. This may be
required during UPS maintenance procedures.
The first of this procedure details how to select the Inverter OFF and
power the load from the bypass mains via the Static Switch.
1. From the Default window press the ENTER key: the Main Menu
Window will display:
2. Select FUNCTION and press ENTER key:
Before being allowed into the FUNCTION window you are requested
to enter a password. This is achieved by pressing the UP arrow key
repeatedly until the first digit displays the character required, you then
press the DOWN arrow key once to move on to the second digit. This
action is repeated for all eight digits. When the PASSWORD has been
completed press the ENTER key:
BATTERY
VOLTAGE 432 [V]
CURRENT 001 [A]
CHARGE 000 [%]
NORMAL
OPERATION
13:45.32 24.04.97
MEASUREMENT
>FUNCTION <
MAINTENANCE
SETUP
?
WRITE SAVE
?
?
MOVE EXIT C
INPUT PASSWORD
????????
BATTERY TEST
GENERATOR
PANEL SETUP
>NEXT PAGE <