02/02
48
4.4 Remote Alarm Monitor ( # 690254060700)
When used in conjunction with the Interface board
described previously, the Remote Alarm Monitor enables the auxiliary
alarms signals to be displayed at a remote station up to 200 meters
from the main equipment.
The RAM, which can be mounted either horizontally or vertically
contains a mains-driven power supply for alarm LED annunciation
and displays the following warnings:
Panel
Colour
Normal
state
Interpretation
Inverter ON
Green
ON
Normal operating condition indicating that the load is being supplied by the inverter. This is
not an 'alarm’ indicator.
Utility failure
Red
OFF
When lit, it indicates that the input bypass is out of tolerance or missing.
Battery low
Red
OFF
When lit, it indicates that the battery voltage is below minimum or that the battery circuit
breaker is open.
Bypass ON
Red
OFF
When lit, it indicates that the load is being fed from the bypass supply, possibly due to a UPS
failure.
Maintenance
Red
OFF
When lit, it indicates that the UPS has been selected to operate on the maintenance bypass
and load is unprotected.
Alarm
Red
OFF
This is a ‘common alarm’ and is lit when any of the red leds described above are lit
Table 4-1
An audible warning accompanies any of the above alarm conditions.
This is, however, subject to a short time delay when activated in
conjunction with the 'Utility Failure' and 'Bypass ON' alarms, to
prevent the warning being activated by transient conditions. Pressing
the 'reset' push-button cancels the audible warning but the alarm
indications remain until the conditions is rectified.
4.4.1 Connections
Power supply
The RAM contains a single-phase 220-240 V AC mains-driven power
supply. Power is applied through a standard three-pin mains
connector located in the RAM back panel (plug provided) -use 3-core
0.5 mm cable (minimum). The supply is rated at approximately 4
Watts and fused at 1 A.
It is advised that the power supply is taken from the UPS output,
otherwise in the event of a mains failure the RAM may be inoperative.
Alarm connections
A 9 pin D-type connector with solder points is provided with the RAM.
This connector fits into the 9 pin socket on the back of the RAM and
should be cabled to the Interface Board # 10020112003 fitted to the
UPS, using 9 core, 0.22 mm. (minimum) shielded cable as shown.
The maximum recommended distance is 100 meters.
7400M - Series UPS User Manual
Single Module and 1+N Parallel System