Pipe diameter
/inch(mm)
Nut Size
/inch(mm)
Tightening Torque
ft-lbs
N-m
1/4(6.35)
1/4(17)
11 to 15
15 to 20
3/8(9.5)
3/8(22)
22 to 26
30 to 35
1/2(12.7)
1/2(25)
37 to 41
50 to 55
5/8(15.9)
3/4(19)
5/8(29)
3/4(32)
44 to 48
52 to 55
60 to 65
70 to 75
9
Installation Instructions
3. Piping Connections to Outdoor Unit
Service
Valve Cover
Apply a small amount of refrigerant oil to the flare connection
on the refrigerant pipe.
Properly align piping and tighten flare nut using a standard
wrench and a torque wrench as shown in the indoor piping section.
Carefully tighten flare nuts to correct torque level referring to the
following Torque Table:
Carefully bend and adjust length of refrigerant pipes to meet
outdoor unit service valves connection with proper tools to
avoid kinks.
Remove service valve cover( if provided) to access the service
valves and refrigerant ports.
Torque Table
Note: Over tightening may damage flare connections and cause leaks.
WARNING
Florida wind load requirements state that outdoor unit must be anchored to
concrete pad using four 3/8-in diameter power wedge bolt plus(or equivalent)
with 1-in diameter fender washers. Anchor bolts must be embedded into
3000 PSI minimum concrete at a distance of 4 1/2- in from any concrete edge.
The concrete thickness must exceed 1.5 times the anchor depth.
Summary of Contents for 12K
Page 1: ...INSTALLATION ...
Page 28: ......
Page 29: ......
Page 56: ......
Page 57: ...意 大 利 文 INSTALLATION ...
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ...T 25A 250V ...
Page 75: ......
Page 76: ...3 Preparación antes del uso Nota ...
Page 78: ......
Page 79: ...6 ...
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ...REMOTE ...
Page 97: ......
Page 98: ......
Page 108: ......