Installation Instructions
Caution:
1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, refer to the circuit diagram posted on the inside of the access door .
2. Comfirm that the cable thickness is as specified in the power source specification.
3. Check the wires and make sure that they are all tightly fastened after cable connection.
4. Be sure to install an earth leakage circuit breaker in wet or moist areas.
Cable Specifications
Attention:
The plug must be accessible even after the installation of the appliance in case there is a need
to disconnect it. If not possible, connect appliance to a double-pole switching device with
contact separation of at least 3 mm placed in an accessible position even after installation.
Connecting of the Cable
Indoor Unit
Connect the power cord to the indoor unit by connecting
the wires to the terminals on the control board individually
in accordance with the outdoor unit connection.
Note: For some models, it is necessary to remove the cabinet to
connect to the indoor unit terminal.
The figures in this manual are based on the external
view of a standard model. Consequently, the shape
may differ from that of the air conditioner you have
selected.
Chassis
Cabinet
Front panel Terminal (inside)
Indoor unit
Power and Wiring
capacity(Btuh)
Power cord
Power connecting cord
Type
Normal cross-
sectional areas
Type
Normal cross-
sectional areas
9K-12K(208/230V)
SJ TW
3X16 AWG
SJ TW
4X18 AWG
18K(208/230V)
SJ TW
3X14 AWG
SJ TW
4X18 AWG
24K-36K(208/230V)
SJ TW
3X12 AWG
SJ TW
4X18 AWG
9K,12K(115V)
SJ TW
3X14 AWG
SJ TW
4X18 AWG
Outdoor unit Different-diameter joint
indoor unit
Connect pipes using different-diameter joint
If the diameter of connection pipe does not match the port size of outdoor unit, select
proper different-diameter joints in the accessory according to the following table.
Name
Quantity
Purpose
1
Change pipe diameter from
1/4(6.35) to 3/8(9.52)
1
Change pipe diameter from
3/8(9.52) to 5/8(15.88)
1
Change pipe diameter from
3/8(9.52) to 1/2(12.7) mm
Summary of Contents for 12K
Page 1: ...INSTALLATION ...
Page 28: ......
Page 29: ......
Page 56: ......
Page 57: ...意 大 利 文 INSTALLATION ...
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ...T 25A 250V ...
Page 75: ......
Page 76: ...3 Preparación antes del uso Nota ...
Page 78: ......
Page 79: ...6 ...
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ...REMOTE ...
Page 97: ......
Page 98: ......
Page 108: ......