For facilities below 40% relative humidity, it is recommended to use grounding straps
when contacting the equipment to avoid the risk of Electrostatic discharge (ESD), which
can harm electronic equipment.
As part of an ongoing monitoring process for the corrosiveness of the environment, it is
recommended to place copper and silver coupons (per ISA 71.04-1985, Section 6.1
Reactivity), in airstreams representative of those in the data center. The monthly
reactivity rate of the coupons should be less than 300 Angstroms. When monitored
reactivity rate is exceeded, the coupon should be analyzed for material species and a
corrective mitigation process put in place.
DAE Technical Specifications and Operating Limits
26
EMC CloudBoost 100
2.0
Hardware Component Replacement Guide