EMC INDUSTRIAL GROUP LTD
Internal Signals
MW61A_IM_ALL_SV6.09d_en
29/47
Q23126 zero weight
8220
kg,t,g
Displays the amount of weight that has been zeroed out since the last zero calibration.
Weight motion
Q23131 motion detection band
(set to 0 to disable) [0 to 50]
8230, g5
12
3.0 divs
The weight is at in motion if it is outside the ‘motion detection band’ for longer than the ‘motion de-
tection time’.
Q23132 motion detection time
[0.2 to 2]
8232, g5
1.0 s
The weight is at in motion if it is outside the ‘motion detection band’ for longer than the ‘motion de-
tection time’.
Peak weight etc.
Q23141 peak weight
8240, g5
kg,t,g
Displays the peak weight (automatically captured) since the last time it was reset.
Q23142 absolute weight
8242, g5
kg,t,g
Displays the absolute value of the net weight (ie negative weights are shown as positive weights).
Flowrate
Q2333 flowrate
8762, g6
t/h,kg/h
Displays the flowrate.
Q2335 flowrate response
[10s, 14s, 20s, 30s, 50s]
8296, g6
normal=1
Sets the how quickly the flowrate is determined. For systems with a small weight change signal, the
flowrate may be more stable when this setting is higher, but it will take longer to reach a steady
flowrate reading.
Totaliser
Q2344 total weight
8730, g6
0.00 kg,t,g
Displays the weight totaliser. The total is retained after a power failure.
Q2345 running total
8732, g6
0.00 kg,t,g
Displays a running weight total. This total is not reset by the RESET TOTAL operation.
Q2346 totaliser digits
8320, g6
6
Sets the number of digits the totaliser counts to.
Limits
Limit 1
Q23511 limit 1 source (modbus address of signal)
8350, g7
Set this to the modbus address of the signal that will be compared with the setpoint.
Q23512 limit 1 mode
8354, g7
high limit = 0
Sets the limit operating mode.
limit mode
description
0
high limit
1
low limit
2
outside band
3
inside band
4
fill control
5
empty control
Q23513 limit 1 delay
8352, g7
0.00 s
Sets a delay to activate or de-active the limit.
Q23514 setpoint 1
8330, g7
Sets the limit value.
Q23515 setpoint 1 preact
8356
Sets the preact value.
Limit 2
Q23521 limit 2 source (modbus address of signal)
8360, g7
Q23522 limit 2 mode
8364, g7
low limit = 1
Q23523 limit 2 delay
8362, g7
0.00 s
Q23524 setpoint 2
8332, g7
Q23525 setpoint 2 preact
8366