Embedded Data Systems MN-RTD4W-H Manual Download Page 10

 

© 2020 Embedded Data Systems, LLC.; 2019 Fortune Drive; Lawrenceburg, KY 40342; Phone/Fax 502-859-5490     10 / 10 

EN-USERMAN MN-RTD4W-H V1.0  10.09.2020 

Regulatory Compliance 

FEDERAL COMMUNICATIONS COMMISSION (FCC) COMPLIANCE STATEMENT 

This device complies with part 15 of the FCC Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any 
interference received, including interference that may cause undesired operation. 
 
 

INDUSTRY CANADA (IC) COMPLIANCE STATEMENT 

This Class B digital apparatus complies with Canadian ICES-003.  
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. 
 
 
 

EUROPEAN COMMUNITY (EC) DIRECTIVES CONFORMITY 

APPLICATION OF COUNCIL DIRECTIVE 2004/108/EC Standard to which Conformity is Declared: 
 

 

EN 61326-1:2006    

 

 

(Emmissions) 

 

 

EN 61326-2-3:2006  

 

 

(Immunity) 

 

 

EN 61000-3-2:2006+A1:2009+A2:2009  (Harmonics) 

 

 

EN 61000-3-3:2008  

 

 

(Flicker) 

 

 

 

 

 

 

 
Caution: The manufacturer is not responsible for any radio or television interference caused by using 
other than recommended cables or by unauthorized changes or modifications to this equipment. 
Unauthorized changes or modifications could void the user’s authority to operate this equipment. 

 

Summary of Contents for MN-RTD4W-H

Page 1: ...or s transmission range RTD fault detection and screw down terminals Together these features offer an efficient and flexible system for monitoring wide temperature ranges from 200 to 800 C RTD dependent the temperature at multiple indoor and outdoor locations Part Numbers Description MOQ MN RTD4W H Two 4 Wire RTD Connections with Battery Power 1 MN RTD4W H PLUG Two 4 Wire RTD Connections Plugin Po...

Page 2: ...will flash rapidly indicating that the sensor is now in an active state 8 Close the enclosure making sure that the screw down terminal is on the opposite side of the cable grommet to improve wireless performance by keeping the cables away from the wireless antenna 9 Lightly pull the cable to remove excess cabling from within the enclosure 10 Take the 4 screws included in your hardware bag and secu...

Page 3: ...er higher numbers equate to stronger signals Due to hardware limitations the highest number that can be displayed is 34 dBm However the actual signal strength may be much higher DeviceRSSI This indicates the strength of the radio signal at the sensor Due to hardware limitations the highest number that can be displayed is 34 dBm however the actual signal strength may be much higher Address This is ...

Page 4: ...dicates the oldest unsent buffered packet in the buffer When the BufferHeadPointer and BufferTailPointer are the same the buffer is empty RTD1ValueCalibration RTD2ValueCalibration It contains the factory calibration for the input channels Factory Reset Web soft reset Writing anything to the FactoryReset location will return all parameters except for the UserName and the Network Key to factory defa...

Page 5: ...r increments until the counter is reset MessagePacketRetries The number of times wireless packets had to be resent due to no acknowledgment being received The maximum is 65535 after which it no longer increments until the counter is reset MessageFailures When no acknowledgment is received the packet is resent After 4 retries the message has failed The counter increments when a failure has occurred...

Page 6: ... EDS RTD Sensor UserName owd_EDS2030_Tag owd_EDS2030_Data Description RTD Sensor with high power transceiver and power management Name EDS2030 Name EUI 801F12FFFECB7C0C EUI ControllerRSSI Units dBm 41 ControllerRSSI Address 1 Address Repeater 0 Repeater TimeStamp 2020 05 05 12 19 31 TimeStamp RTD1Temperature 250 000 RTD1Temperature RTD1Ohms 0 000 RTD1Ohms RTD1Fault 1 RTD1Fault RTD1CalibrationValue...

Page 7: ...n be maximized by reading sending the sensor data as infrequently as possible Battery life is highly variable on a number of parameters 1 How often data is read sent 2 Extreme temperatures reduce the useful life of the battery 3 If the sensor is sending data through a repeater battery life will be reduced because the sensor has to wait longer for the acknowledgment 4 If the sensor has to reconnect...

Page 8: ...ces When the name and password is requested enter admin for the name and eds for the password A page similar to below will appear 5 Insert AA batteries into sensor Once this is done the sensor will appear 7 in the Unlinked Devices section 6 Click the unlinked sensor A window will pop up confirming you want to link the sensor Click OK The sensor will move to the Linked Devices section upon its next...

Page 9: ...Temperature humidity external probe support 2K memory buffer high power radio buffer only mode EDS2042 Up to 3 waterproof external temperature probes 2K memory buffer high power radio buffer only mode EDS REPEATER DEVICE IDS ID Features EDS2101 MeshNet Repeater with high power radio SPECIFICATIONS PARAMETER MIN TYP MAX UNITS Operating Temperature Range 40 85 C Accuracy 200 to 800 with Input at 21 ...

Page 10: ... COMPLIANCE STATEMENT This Class B digital apparatus complies with Canadian ICES 003 Cet appareil numérique de la classe B est conforme à la norme NMB 003 du Canada EUROPEAN COMMUNITY EC DIRECTIVES CONFORMITY APPLICATION OF COUNCIL DIRECTIVE 2004 108 EC Standard to which Conformity is Declared EN 61326 1 2006 Emmissions EN 61326 2 3 2006 Immunity EN 61000 3 2 2006 A1 2009 A2 2009 Harmonics EN 6100...

Reviews: