41
GS42
2 x external voltage or current
0-100mV DC
0.02/0.03mV
±0.06mV
GS44
4 x external voltage or current
0-1V DC
0.25mV
±0.5mV
GS44AVE
As GS44 but with averaging function
0-10V DC
2.50mV
±5mV
0-20mA DC
~5uA
20uA
4-20mA DC
0.05%
0.1%
GD43E
1 x external RH and temperature
(RHT10E)
as GS13E
1 x voltage / current
as GS42
1 x external thermistor temperature
as GS31
GD43JScf
1 x external RH and temperature
(EplusE EE68)
as GD13J
1 x voltage / current for pyranometer
0-30mV
0.1%
±30uV
1 x external thermistor temperature
as GS31
GD47/GW
47
1 x built-in RH and temperature
as GD10
1 x built-in CO2
0-5000ppm
3%
±50ppm
1 x built-in 12VDC supply monitor
GS52/GD
52
2 x 2 or 4 wire Pt100 temperature
-100 to
200ºC
0.1ºC
±0.3ºC
GS52H
2 x 2 or 4 wire Pt100 temperature
0 to 300ºC
0.1ºC
±0.3ºC
GC60
2 x state indications
GC60F
2 x state indications for flood sensors
only
GC60Y
As GC60 with mark/space ration of
event during TX interval
GC62EX
2 x pulse inputs for connection to
domestic gas meter
GC62/GC
62a
2 x pulse inputs (/a inverted input)
GD67
7 x pulse inputs
GD68/GD
68a
8 x pulse inputs (/a inverted input)
GL-70
1 x built-in temperature and RH
As GC10
1 x visible light
0-4,000 Lux
0.1Lux
0-200 KLux
0.01KLux
1 x UV light
0-5000
mW/m²
0-10,000
µW/Lumen
GD72E
1 x external temperature and RH
As GD13E
1 x external visible light (LS50 or LS70)
As GL-70
1 x external ultraviolet (LS70 only)
As GL-70