30
11.4.1
Communications
Example request to retrieve holding register 100 (set up to contain the raw
value from channel 1) from node address 6:
Slave Address
06
Function
03
Starting Address Hi 00
Starting Address Lo 64
No. of Registers Hi
00
No. of Registers Lo
01
CRC Hi
c4
CRC Lo
62
Response from RC250:
Slave Address
06
Function
03
Byte count
02
Raw Value Hi
06
Raw Value Lo
2b (in decimal, 1579)
CRC Hi
4e
CRC Lo
3b
Example request to retrieve holding register 200-201 (set up to contain the
scaled values from channels 1 and 2) from node address 6:
Slave Address
06
Function
03
Starting Address Hi 00
Starting Address Lo c8
No. of Registers Hi
00
No. of Registers Lo
02
Response from RC250:
Slave Address
06
Function
03
Byte count
04 (2 readings, so 4 bytes)
Raw Value Hi
00
Raw Value Lo
e6 (in decimal, 230 - meaning 23.0 degrees)
Raw Value Hi
01
Raw Value Lo
ed (in decimal, 493 - meaning 49.3 %RH)
CRC Hi
ac
CRC Lo
d9