Assembly Instructions
5
Page 54 of 97
Operating Instructions
enCore FC1
Characteristics:
•
an intrinsically safe, galvanically isolated input safe circuits of the
category [Ex ib Gb] II C for transmitter with HART interface;
an active signal and protocol converter integrated in input as
“ssociated electrical equipment” according to EN50020
•
Multidrop mode:
4 Transmitters (max.)
Burst mode:
1 Transmitter
•
maximum cable length:
250 m
Hints on parameterization
Branch
<device> – Basic System – I/O boards –
Board <x>: ExMFE5
Set the following value:
•
channel
P1+ P1−
: type
HART channel
With this, the operating mode of the channel is set correctly for
connecting the HART transmitters.
The following HART modes are possible:
•
Multidrop mode (max. 4 transmitters)
Note that the HART device cannot be operated using the
HART address
zero (
0
).
•
Burst mode (max. 1 transmitter)
Set the burst mode, as you parameterize the
HART address
zero (
0
) for the HART device.