• Underground Installation must comply with the required
standard for termination to Metallic risers.
• Underground Installation must comply with the required
separation standard for Consumer Gas Piping.
• EPS Crimp Gas Fittings must be wrapped and protected
using suitable and verified processes for all in ground
installations and corrosive environments.
Proprietary Gas System Identification:
EPS Crimp Gas PEX-AL Piping system has an identification
Tag as part of its Product Range and must be permanently
attached adjacent to the gas meter or LP Gas cylinder to
identify the system installed on every installation as detailed
in AS/NZS 5601. Do not attach this signage plate to any gas
cylinder or other movable object.
Provision for Pipe Reversion:
As detailed in AS/NZS 5601, in certain installations in some
building types it is mandatory for the installation of reversion
fittings to allow for Proprietary Gas Piping systems like EPS
Crimp Gas to be extended or additions made for future
application. A Reversion Fitting allows for the connection of
a Proprietary system to be adapted to a standard Thread or
Copper tube. The EPS Crimp Gas PEX-AL Piping system
Product Range includes the three variants of Reversion
fittings as detailed in the standard.
* Elson Lead Free copper alloy products are 99.9% Lead Free and contain less than 0.1% Lead by weight.
25
EPS
LEAD FREE*
CRIMP
GAS - Installation Requirements
99.9% Lead Free
< 0.1% Pb
EPS PEX