Behaviour in case of alarm

Leakage sensor Leak

 • Version: 03.08.2017 • Errors and technical modifications subject to change without notice.

1. Disconnect the device from voltage supply (disconnect the mains plug). 
2. Open the casing of the evaluation unit (four screws under the cover and in the cor-

ners of the casing)

3. Replace the seal on the alarm output with the enclosed cable bushing and insert 

the alarm line into the casing.

4. Connect the output device to the relay contact. Please observe the 

internal view

 in 

the figure below.

5. Close the casing.
6. Connect the mains supply line. Line voltage 230 V AC, 50 Hz.
7. The device is ready for operation.

3.

Behaviour in case of alarm

The alarm will be triggered if there is water between the electrodes of the probe for
more than 3 seconds. If there is no more water contact detected on the electrodes, the
alarm will continue for 1 additional minute (follow-up time).

Operation 
state

Water 
between the 
electrodes?

Beeping 
sound (once 
per second)

‘Alarm’ 
LED (red)

Output relay 
setting

No alarm

No

No

off

NC – Com

Alarm

Yes

sustained

on

NO – Com

Alarm
Follow-up 
time

no (1 minute fol-
low-up time)

short:

on

NO – Com

Fig. 4 Inside view
1) Mains supply line (mains 

supply 230 V AC, 50 Hz)

2) Bushing for alarm output line
3) BNC terminal for the probe
4) Loudspeaker
5) LEDs: 

Alarm (red during alarm and 
follow-up time), 
Power (green)

6) Alarm output: 

potential-free changeover 
contact NC/Com/NO

2

5

1

6

3

4

Summary of Contents for Leak

Page 1: ...installation instructions Item number 30161 EN Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Tel 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax...

Page 2: ...he evaluation unit during a water alarm sustained beeping tone Short beeping during the follow up time 1 minute after the end of the alarm Output for alarm reporting potential free changeover contact...

Page 3: ...against unintentional use if it can be assumed that risk free operation is no longer guaranteed The device is only to be used for its intended purpose Any improper modification or failure to follow th...

Page 4: ...o the wall with mounting brackets 2 3 Probe placement The electrode probe is placed on the floor with the contacts facing downwards Ideally the probe should be located in a place that in case of water...

Page 5: ...output use If the alarm output is used the installation testing commissioning and troubleshooting of the unit may only be performed by an electrician pursuant to VDE 0100 DANGER Risk to life from liv...

Page 6: ...z 7 The device is ready for operation 3 Behaviour in case of alarm The alarm will be triggered if there is water between the electrodes of the probe for more than 3 seconds If there is no more water c...

Page 7: ...tact the evaluation unit produces sustained beeping sounds once per second The beeping sounds are shorter during the follow up time 3 2 Output Fig 5 If no alarm is active Contact between NC Normally C...

Reviews: