Description

Leakage sensor Leak

 • Version: 03.08.2017 • Errors and technical modifications subject to change without notice.

1.

Description

The 

Leakage sensor Leak

 includes an evaluation unit and a probe. If there is water

between the electrodes of the probe, the evaluation unit produces an acoustic alarm.
Additionally, the alarm output of the evaluation unit switches on. The output can be
used to transmit the alarm signal to other systems (e.g. klaxons, light indicators, stop
valves, building control system, alarm system). The changeover contact design of the
output makes it possible to detect wire breakage in the alarm line by suitable systems.

Functions:

Detection of water on the probe

Acoustic alarm signal by the evaluation unit during a water alarm (sustained 
beeping tone). Short beeping during the follow-up time (1 minute after the end 
of the alarm).

Output for alarm reporting (potential-free changeover contact)

1.1. Deliverables

Evaluation unit with mains power supply

Probe  with  BNC  cable

Cable guide for alarm output

1.2. Technical specifications

1.2.1. Analysis unit

The product is compliant with the provisions of EC guidelines.

Casing

Plastic

Colour

Grey

Installation

Surface mounted

Protection category

IP 20

Dimensions 

approx. 118 × 86 × 65 (W × H × D, mm),

Weight

approx. 460 g

Ambient temperature

Operation -20…+70 °C, storage -55…+90°C.

Ambient humidity

max. 95 % RH, avoid condensation

Operating voltage

230 V AC, 50 Hz

Power consumption

no alarm:    approx. 1 W
with alarm: approx. 4 W

Probe input

1 x electrode probe, 
      plug-in BNC terminal

Alarm output

1 × potential-free changeover contact, 
      max. 230 V AC / 3 A,
      max. 30 V DC / 3 A,
      Connector NC/Com/NO

Summary of Contents for Leak

Page 1: ...installation instructions Item number 30161 EN Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Tel 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax...

Page 2: ...he evaluation unit during a water alarm sustained beeping tone Short beeping during the follow up time 1 minute after the end of the alarm Output for alarm reporting potential free changeover contact...

Page 3: ...against unintentional use if it can be assumed that risk free operation is no longer guaranteed The device is only to be used for its intended purpose Any improper modification or failure to follow th...

Page 4: ...o the wall with mounting brackets 2 3 Probe placement The electrode probe is placed on the floor with the contacts facing downwards Ideally the probe should be located in a place that in case of water...

Page 5: ...output use If the alarm output is used the installation testing commissioning and troubleshooting of the unit may only be performed by an electrician pursuant to VDE 0100 DANGER Risk to life from liv...

Page 6: ...z 7 The device is ready for operation 3 Behaviour in case of alarm The alarm will be triggered if there is water between the electrodes of the probe for more than 3 seconds If there is no more water c...

Page 7: ...tact the evaluation unit produces sustained beeping sounds once per second The beeping sounds are shorter during the follow up time 3 2 Output Fig 5 If no alarm is active Contact between NC Normally C...