7
Transfer protocol
Sensor KNX T-UP gl
• Version: 05.09.2022 • Technical changes and errors excepted.
34
Temp.control: Switch. (Heating = 0
| Cooling = 1)
Input
-RC-
[1.1]
DPT_Switch
1 Bit
35
Temp.control: Setpoint Comfort
heating
Input /
Output
RWCT [9.1]
DPT_-
Value_Temp
2 Bytes
36
Temp.control: Setpoint Comfort
heat.(1:+ | 0:-)
Input
-RC-
[1.1]
DPT_Switch
1 Bit
37
Temp.control: Setpoint Comfort
cooling
Input /
Output
RWCT [9.1]
DPT_-
Value_Temp
2 Bytes
38
Temp.control: Setpoint Comfort
cool.(1:+ | 0:-)
Input
-RC-
[1.1]
DPT_Switch
1 Bit
39
Temp.control: Basic 16-bit setpoint
shift
Input /
Output
RWCT [9.1]
DPT_-
Value_Temp
2 Bytes
40
Temp.control: Setpoint Standby
heating
Input /
Output
RWCT [9.1]
DPT_-
Value_Temp
2 Bytes
41
Temp.control: Setpoint Standby
heat.(1:+ | 0:-)
Input
-RC-
[1.1]
DPT_Switch
1 Bit
42
Temp.control: Setpoint Standby
cooling
Input /
Output
RWCT [9.1]
DPT_-
Value_Temp
2 Bytes
43
Temp.control: Setpoint Standby
cool. (1:+ | 0:-)
Input
-RC-
[1.1]
DPT_Switch
1 Bit
44
Temp.control: Setpoint Eco hea-
ting
Input /
Output
RWCT [9.1]
DPT_-
Value_Temp
2 Bytes
45
Temp.control: Setpoint Eco hea-
ting (1:+ | 0:-)
Input
-RC-
[1.1]
DPT_Switch
1 Bit
46
Temp.control: Setpoint Eco coo-
ling
Input /
Output
RWCT [9.1]
DPT_-
Value_Temp
2 Bytes
47
Temp.control: Setpoint Eco coo-
ling (1:+ | 0:-)
Input
-RC-
[1.1]
DPT_Switch
1 Bit
48
Temp.control: Control variable
heating (level 1)
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
49
Temp.control: Control variable
heating (level 2)
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
50
Temp.control: Control variable
cooling (level 1)
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
51
Temp.control: Control variable
cooling (level 2)
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
52
Temp.control: Status Heat. level 1
(1=ON|0=OFF)
Output
R-CT
[1.1]
DPT_Switch
1 Bit
No
Text
Function
Flags
DPT Typ
Size