18
Parameter setting
Sensor KNX T-UP gl
• Version: 05.09.2022 • Technical changes and errors excepted.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is
set.
If the comfort setpoint is used as the basis without a switching object, a dead zone is
specified for the control mode "heating
and
cooling" to avoid direct switching from
heating to cooling.
Standby setpoint
Standby mode is usually used for daytime mode when people are absent.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is
set.
Eco setpoint
Eco mode is usually used for night mode.
Starting heating/cooling setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 210
Minimum base setpoint (in 0.1°C)
-300…800; 160
Maximum base setpoint (in 0.1°C)
-300…800; 280
Reduction by up to (in 0.1°C)
1…100; 50
Increase by up to (in 0.1°C)
1…100; 50
Dead zone between heating and cooling in
0,1°C
(only if both heating AND cooling are used)
1…100; 50
Starting heating setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 180
Starting heating setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 240
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
-300…800; 280
Max. object value heating/cooling
(in 0.1 °C)
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 30
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 30