8
Transfer protocol
Sensor KNX T-UP gl
• Version: 05.09.2022 • Technical changes and errors excepted.
53
Temp.control: Status Heat. level 2
(1=ON|0=OFF)
Output
R-CT
[1.1]
DPT_Switch
1 Bit
54
Temp.control: Status Cool. level 1
(1=ON|0=OFF)
Output
R-CT
[1.1]
DPT_Switch
1 Bit
55
Temp.control: Status Cool. level 2
(1=ON|0=OFF)
Output
R-CT
[1.1]
DPT_Switch
1 Bit
56
Temp.control: Comfort extension
status
Input /
Output
RWCT [1.1]
DPT_Switch
1 Bit
57
Temp.control: Comfort Extension
time
Input
RWCT [7.5]
DPT_TimePeri-
odSec
2 Bytes
58
Temperature control: Variable for
4/6-way valve
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
131
CO2 control: Act. variable ventila-
tion (1.stage)
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
133
CO2 control: Status ventilation
(1=ON | 0=OFF)
Output
R-CT
[1.1]
DPT_Switch
1 Bit
134
CO2 control: Status ventilation 2
(1=ON | 0=OFF)
Output
R-CT
[1.1]
DPT_Switch
1 Bit
135
Actuating variable comparator 1:
Input 1
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
136
Actuating variable comparator 1:
Input 2
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
137
Actuating variable comparator 1:
Input 3
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
138
Actuating variable comparator 1:
Input 4
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
139
Actuating variable comparator 1:
Input 5
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
140
Actuating variable comparator 1:
Output
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
141
Actuating variable comparator 1:
Block
Output
-RC-
[1.2]
DPT_Bool
1 Bit
142
Actuating variable comparator 2:
Input 1
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
143
Actuating variable comparator 2:
Input 2
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
144
Actuating variable comparator 2:
Input 3
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
145
Actuating variable comparator 2:
Input 4
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
146
Actuating variable comparator 2:
Input 5
Input
-RC-
[5.1]
DPT_Scaling
1 Byte
No
Text
Function
Flags
DPT Typ
Size