23
Setting parameters
KNX TH65-AP thermal hygrometer
• Version: 27.01.2020 • Technical changes and errors excepted.
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
Night reduction
Decide when night reduction is to be activated.
If the setpoint is set via parameters:
Set the setpoint for heating and/or cooling.
If the setpoint is set via communication object:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
When blocked, the control variable shall
• not be sent
• send a specific value
Value (in %)
(if a value is sent)
0...100
Use night reduction
No • Yes
Night reduction for object value
• 1 = active | 0 = inactive
• 0 = active | 1 = inactive
Activation object value
before first call
0 • 1
Specified setpoint using
Parameter • Communication object
Specified setpoint using
Parameter
Setpoint heating in 0.1°C
(if the heating regulator is being used)
-300 … 800; 180
Setpoint cooling in 0.1°C
(if the cooling regulator is being used)
-300 … 800; 260
Specified setpoint using
Communication object
The last communicated value should
• not be retained
• be retained after power restoration
• be retained after power restoration and
programming (not to be used for
first commissioning)
Start setpoint heating in 0.1°C
valid until first call
(if the heating regulator is being used and
only if the last retained value is "not"
retained, or retained "after power restora-
tion")
-300 … 800
Limitation of object value H(min)\r\n
in 0.1°C
-300 … 800
Limitation of object value H(max)\r\n
in 0.1°C
-300 … 800