17
Setting parameters
KNX TH65-AP thermal hygrometer
• Version: 27.01.2020 • Technical changes and errors excepted.
General control
Define the
type of control
. Heating and/or cooling may be controlled in two levels.
Then configure a temperature control
block
using the blocking object.
Specify when the current control variables are to be sent to the bus. Periodic transmis-
sion is safer if a message does not reach a recipient. You may also set up periodical
monitoring by the actuator with this setting.
The status object reports the current status of the control variable (0% = OFF,
>0% = ON) and may for example be used for visualisation, or to switch off the heating
pump as soon as the heating is switched off.
Set the way in which switching from heating to cooling is to take place.
Type of control
• Single level heating
• Dual-level heating
• Single-level cooling
• Dual-level cooling
• Single-level h single-level cooling
• Dual-level h single-level cooling
• Dual-level h dual-level cooling
Behaviour of the blocking object with value
• 1 = Blocking regulation |
0 = Releasing regulation
• 0 = Blocking regulation |
1 = Releasing regulation
Send control variable
• on change
• on change and periodically
Send cycle
(is sent only if "periodically" is selected)
5 s … 2 h
Send status object(s)
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Send cycle
(is sent only if "periodically" is selected)
5 s … 2 h
Switching between heating and cooling
• By means of dead zone
• By means of switching object
Dead zone between heating and cooling
(in 0.1°C)
(when switched by means of a "dead zone")
1 … 100; 50
Value of the switching object before first
call
(when switched by means of a switching
object)
0 • 1
Summary of Contents for 70184
Page 1: ...EN Installation and Adjustment KNXTH65 AP Thermo Hygrometer Item number 70184 ...
Page 2: ......
Page 35: ......