19
Parameter settings
Temperature Sensor KNX T-UN
• Version: 27.01.2020 • Technical changes and errors excepted.
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
Night reduction
Activate night reduction to set the night time operation of the heating/cooling.
Set for which object night reduction is active.
Specified setpoint per parameter:
Set the setpoint for the heating and/or cooling.
Specifying a setpoint per communications object:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
When blocked, the control variable shall
• not be sent
• send a specific value
Value
only if a value is sent
0 • 1
Use night reduction
No • Yes
Use night reduction
Yes
Night reduction for object value
• 1 = active | 0 = inactive
• 0 = active | 1 = inactive
Activation object value
before first call
0 • 1
Specified setpoint using
Parameter
Setpoint heating in 0.1°C
(if the heating regulator is being used)
-300 … 800; 180
Setpoint cooling in 0.1°C
(if the cooling regulator is being used)
-300 … 800; 260
Specified setpoint using
Communications object
The last communicated value
should
• never be retained
• be retained after power restoration
• be retained after power restoration and
programming (not to be used for
first commissioning)
Start setpoint heating in 0.1°C
valid until first call
(if the heating regulator is being used and
only if the last retained value is "not"
retained, or retained "after power restora-
tion")
-300 … 800; 180
Limitation of object value H(min)\r\n in
0.1°C
-300 … 800; 140