35
Parameter setting
Sensors Intra-Sewi KNX TH-L-Pr and Intra-Sewi KNX L-Pr
• Version: 30.08.2018 • Technical changes and errors excepted.
Settings for brightness dependent motion detection:
The
brightness dependent motion detection
can be used via separate threshold
values for switch-on and switch-off or dependent on daylight. The separate threshold
values are ideal for controlling the light in rooms which are only illuminated by artifi-
cial light. The daylight dependent control is ideal for rooms with daylight and artificial
light.
For
daylight dependent motion detection with separate switch-on and
switch-off threshold values
activate, as required, the objects for setting the th-
reshold values. Then specify the switch-on and switch-off values (brightness range).
The switch-on value is the value, below which the room should be lit in the event of
movement. The switch-off value should be higher than the brightness value of the ar-
tificially lit room.
For the
daylight dependent motion detection
activate, as required, the objects for
setting the threshold values/hysteresis and waiting period. Then specify the switch-on
value. This is the value, below which the room should be lit in the event of movement.
The switch-off value is derived from the brightness measurement that is performed by
the sensor at the end of the waiting period. Set the waiting period such that after it all
lamps are set to the final brightness. The hysteresis is added to the measured bright-
ness value. If the room brightness later exceeds this total value because the room is
illuminated by daylight, the motion control is switched off.
Motion detection
brightness dependent
Type of brightness dependency
• separate switch-on and switch-off values
• daylight dependent
Type of brightness dependency
•
separate switch-on and switch-off
values
Threshold values can be set via objects
No • Yes
Switch on sensor below
Lux
1...5000; 200
Switch off sensor below
Lux
1...5000; 500
Type of brightness dependency
•
Daylight dependent
Threshold values and hysteresis can be set
via objects
No • Yes
Waiting period can be set via objects
No • Yes
Switch on sensor below
Lux
1...5000; 200
Switch off sensor, at the earliest
after a waiting period of seconds
0...600; 5
after motion detection and above
measured brightness plus hysteresis
in Lux
1...5000; 200