27
Parameter setting
Sensors Intra-Sewi KNX TH-L-Pr and Intra-Sewi KNX L-Pr
• Version: 30.08.2018 • Technical changes and errors excepted.
5.
Parameter setting
5.1.
Behaviour on power failure/ restoration of
power
Behaviour following a failure of the bus power supply:
The device sends nothing.
Behaviour on bus restoration of power and following programming or reset:
The device sends all outputs according to their send behaviour set in the parameters
with the delays established in the "General settings" parameter block.
5.2.
General settings
Set basic characteristics for the data transfer.
5.3.
Brightness Measurement
The sensor detects the brightness in rooms, for example for controlling lights.
Set the
sending pattern
for the measured brightness.
The brightness reading can be
corrected
in order to compensate for a dull or bright
point of installation for the sensor.
Send delay after reset/bus restoration for:
Measured values
5 s • ... • 300 s
Threshold values and switching outputs
5 s • ... • 300 s
Controller objects
5 s • ... • 300 s
Comparator and logic objects
5 s • ... • 300 s
Maximum telegram rate
• 1 message per second
• ...
• 10 messages per second
• ...
• 50 messages per second
Sending pattern
• never
• periodically
• on change
• on change and periodically
at and above change in %
(if sent on change)
1 ... 100; 20
Send cycle
(if sent periodically)
5 s ... 2 h
Use reading correction
No • Yes