20
Transfer protocol
Sensors Intra-Sewi KNX TH-L-Pr and Intra-Sewi KNX L-Pr
• Version: 30.08.2018 • Technical changes and errors excepted.
103 Temp. threshold value 4: (1:+ |
0:-)
Input
-WC- [1.1]
DPT_Switch
1 Bit
104 Temp. thresh. val. 4: Switching
delay from 0 to 1
Input
-WC- [7.5]
DPT_TimePeriodSec
2 Bytes
105 Temp. thresh. val. 4: Switching
delay from 1 to 0
Input
-WC- [7.5]
DPT_TimePeriodSec
2 Bytes
106 Temp. threshold value 4: Swit-
ching output
Output
R-CT
[1.1]
DPT_Switch
1 Bit
107 Temp. threshold value 4: Swit-
ching output block
Input
-WC- [1.1]
DPT_Switch
1 Bit
108 Temp.control: HVAC mode
(priority 1)
Input
-WC- [20.102]
DPT_HVACMode
1 Byte
109 Temp.control: HVAC mode
(priority 2)
Input
-WCT [20.102]
DPT_HVACMode
1 Byte
110 Temp.control: Mode frost/heat
protection activt.
Input
-WCT [1.1]
DPT_Switch
1 Bit
111 Temp.control: Block (1 = Bloc-
king)
Input
-WC- [1.1]
DPT_Switch
1 Bit
112 Temp.control: Current setpoint
Output
R-CT
[9.1]
DPT_Value_Temp
2 Bytes
113 Temp.control: Switch. (0: Hea-
ting | 1: Cooling)
Input
-WC- [1.1]
DPT_Switch
1 Bit
114 Temp.control: Setpoint Com-
fort heating
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
115 Temp.control: Setpoint Com-
fort heat.(1:+ | 0:-)
Input
-WC- [1.1]
DPT_Switch
1 Bit
116 Temp.control: Setpoint Com-
fort cooling
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
117 Temp.control: Setpoint Com-
fort cool.(1:+ | 0:-)
Input
-WC- [1.1]
DPT_Switch
1 Bit
118 Temp.control: Basic 16-bit set-
point shift
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
119 Temp.control: Setpoint Standby
heating
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
120 Temp.control: Setpoint Standby
heat.(1:+ | 0:-)
Input
-WC- [1.1]
DPT_Switch
1 Bit
121 Temp.control: Setpoint Standby
cooling
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
122 Temp.control: Setpoint Standby
cool. (1:+ | 0:-)
Input
-WC- [1.1]
DPT_Switch
1 Bit
123 Temp.control: Setpoint Eco hea-
ting
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
124 Temp.control: Setpoint Eco hea-
ting (1:+ | 0:-)
Input
-WC- [1.1]
DPT_Switch
1 Bit
No. Text
Function Flags Data Point Type