43
Setting the parameters and functions
Fabro KNX Touch Panel
• Version: 13.07.2021 • Technical changes and errors excepted.
Blocking
If necessary, activate the block for the logic output and set what a 1 or 0 at the block
input means and what happens in the event of a block.
Monitoring
If necessary, activate the input monitoring. Set which inputs are to be monitored, at
which intervals the inputs are to be monitored and what value the "monitoring status"
should have, if the monitoring period is exceeded without a feedback being given.
6.11.2.AND logic connection inputs
do not use
Logic input 1
Logic input 1 inverted
Logic input 2
Logic input 2 inverted
Logic input 3
Logic input 3 inverted
Logic input 4
Logic input 4 inverted
Logic input 5
Logic input 5 inverted
Logic input 6
Logic input 6 inverted
Logic input 7
Use block
No • Yes
Assessment of the block object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first Commu-
nication
0 • 1
Output behaviour
when blocking
• Do not send message
• Send block value [see above,
output value if block active]
when released
(with 2 second release delay)
[send value for current logic status]
Use input monitoring
No • Yes
Input monitoring
• 1 • 2 • 3 • 4
• 1 + 2 • 1 + 3 • 1 + 4 • 2 + 3 • 2 + 4 • 3 + 4
• 1 + 2 + 3 • 1 + 2 + 4 • 1 + 3 + 4 • 2 + 3 + 4
• 1 + 2 + 3 + 4
Monitoring period
5 s • ... • 2 h; 1 min
Output behaviour on exceeding the moni-
toring time
• Do not send message
• Send value exceeding [= value of the
parameter "Monitoring period"]