Product Description

Cold Storage Controller with 4 relays 

(TARN: 3 relays) for Solenoid Valve, 

Defrost  heater,  Fan  and/or  Alarm 

Forwarding.  Usable  for  any  kind 

of  cold  storages  such  as  walk-in 

coolers/freezers,  refrigerated  shelfs, 

refrigerated counters, etc.. Depending 

on type, defrost initiating is controlled 

by a cyclic timer or a real time clock. 

Housing  for  panel  mounting,  13mm 

LED-Display.

Accessories 

(please order separately)

Temperature probe TF 201 or TF 501

Parameters

All selectable parameters hold a parameter number (e.g. P03), you will find 

a listing on the next page.

Calling up and editing

Press key 'P' ........................................................parameter number appears 

Use '

/

'  ................................................................ select desired parameter

Press "P" again ........................................................parameter value appears

Use keys '

/

' ............................................................ adjust parameter value

Press 'P' again .................................... value is stored, back to parameter no.

Unlock Keys

To prevent un-authorized persons from editing parameter values, there is a 

locking function which allows only the most important parameters to be changed 

at any time. The access code can entered as follows:

-  Before programming at P41

-  Directly at the parameter to change. If a code is necessary, the display    

  shows "C". Use "

/

" to set the necessary code now and confirm by "P".

If no key is hit for about four minutes, the editing function is locked again.

Auto scrolling

Hold '

/

'-keys to scroll values automatically.

Manual Defrost

Manual defrost can be initiated while the display shows the actual value:

-   Hold '

' for more than 2 seconds = Defrost ON

-  Hold '

' for more than 2 seconds = Defrost OFF.

Reading the controller type

-  Hold key 'P' for more than 2 seconds, the display shows controller type  

   

(

137

 resp. 

138

, at TARN types 

h37

 resp. 

h38

). By pressing "

additionally,  

 

the software version will be displayed. 

Set parameters to factory default (Init)

Switch off supply voltage, press and hold the 'P'-key, switch on supply voltage 

again. Code request "C" appears. Enter "88" and confirm by "P". Now the 

display shows one by one: software- version, date and 'def.', which signifies 

that all parameters are set to default values now.

Error Messages / Error Listing

While a failure the display switches to parameter P40 and shows a code. 

-  Key "P" switches back to the last display 

-  If  multiple  failures  are  present  simultaneously,  codes  can  be  read  by 

"

/

".

Error Codes

E00  ................................... no failure

E01  ............. Control Sensor broken

E02  ......Control Sensor short circuit

E03  ....... Control Sensor Overtemp. 

Technical Data

Supply Voltage  TAR ...................................

12V AC (50/60Hz) / 11-18V DC

 

 

TARN 13xx ...........................................

230V AC (50-60Hz)

 

 

TARN 213xx.........................................

115V AC (50-60Hz)

Power Consumption ............................. TAR: max. 3 VA, TARN: max. 4,4 VA

Relays  Cooling  TAR (UL) .............resistive: 120/240V AC, 10A, 30 k cycles

 

 

 

motor: 120/240V AC, 4A, 30 k cycles  

 

others   TAR (UL) ................resistive: 120/240V AC, 8A, 30 k cycles

   

motor: 125/250V AC, ¼ HP, 30 k cycles

 

Cooling  (TAR, TARN) ........................................... 10A, 80A/10 msec

 

others   (TAR) .............................. 8A res., 3A cosphi=0,4, 250V AC

 

others   (TARN) .....................................................5A res. / 250V AC

 

!! The max. current over terminal 7 (TARN: Terminal 4) may not  

 

increase 12 A !!

Ambient Temperature TAR (UL) .................................... -10..+65°C (14..149°F)

Ambient Temperature TARN ......................................... -10..+55°C (14..131°F)

Storage Temperature ............................................... -30...+70°C (-22...158°F)

Relative Humidity ............................................max. 85% r.H., not condensing

Temperature sensors .............................. TF 201, TF 202 or TF 501 (Pt1000)

Display  .................. LED, 7-segment, red, character height 13mm (.51 inch)

Resolution / Accuracy ................................................0,1°C (0,2°F) / typ. ± 1K 

Control-/Display Range with Temperature Sensor Types

 

TF 201/202 ..................................................-40...+80°C / -40...176°F

 

TF 501 ...................................................-110...+120°C / -166...248°F

Data storage parameters .................................................................

$

20 years

Clock backup (1380-2 only) ........................... typ. 10 days after mains is lost

Alarm Beeper (1370H-2 only) ........................................................2x per sec.

Relay indicators ............................................................................... 3 mm, red

Electrical Connection .................................................screw terminals 2,5mm²

Protection .................................................................................IP 54 from front

Failure codes 

see below

E04  ..... Control Sensor Undertemp.

E05  ............. Defrost Sensor broken

E06  ......Defrost Sensor short circuit

Manual No. 

5311009-03/11e

2

Software Vers. 

 

1370-2: 1.15 / 1380-2: 1.15

Cold Storage Controller

TAR   1370-2

   

(Cyclic Timer)

TAR   1370-2 H

  

(add. Beeper)

TAR   1380-2

   

(Real Time Clock)

TARN  (2)1370-2

   

(Cyclic Timer)

TARN  (2)1380-2

   

(Realtime Clock)

ELEKTRONISCHE  REGELUNGEN  GMBH

Operating Elements

Please read this manual carefully before using the product. The guarantee will lapse in case of 

damage caused by failure to comply with these operating instructions! We shall not be liable 

for any consequent loss! We do not accept liability for personal injury or damage to property 

caused by inadequate handling or non-observance of the safety instructions! The guarantee 

will lapse in such cases. This manual, which is part of the product, has been set up with care 

and our best knowledge, but mistakes may occur. Technical details can be changed without 

notice, especially the software. Please note that the described functions are only valid for units 

containing the software version-number shown on page 1.

ELREHA GmbH

D-68766 Hockenheim, Germany, 

Schwetzinger Str. 103

phone 0 62 05 / 2009-0  -  fax 0 62 05 / 2009-39  -  [email protected]

Please Note Safety Instructions !

Please note supply voltage and changed 

functions when replacing older types !

  New features compared to the older version (without -2)

  - Failures are displayed as error codes now. 

  - Access codes can be entered directly at the parameter. 

  - 3 new parameters added. 

   

- Last actual value stored while defrost  (P38)

   

- Emergency mode (P39), - Current Error + Error Listing (P40)

   

- Codeparameter now is (P41)

Applications

• Cold rooms, refrigeration units,

  refrigerated shelfs, etc. with

• One evaporator

• Evaporator fan

• Defrost heater, Free-Air Defrost,

  Hot Gas Defrost

Abtauung EIN

D ezim alpunkt blinkt

w enn N achtsollw ert aktiv

TAR

Kühlung EIN

W erte

erhöhen

W erte

verringern

P

ELREHA

Alarm

Lüfter EIN

Program -

m ieren /

Aufrufen

Decimal point blinking if 2

nd 

setpoint (night) is active

Programming/

Call up

Cooling ON

Defrost ON

Fan ON

Alarm

Increase 

Values

Decrease 

Values