 Functional Description

Display & Sensors

All temperature values can be displayed in °C or °F 

with a resolution of 0,1K (0,2°F), selectable by 

P21

TF201, TF 202 (PTC) as well as TF501 (Pt1000) 

sensors can be used, but note that this results in 

different temperature ranges. Sensor 2 (Evap. Limit 

Sensor) can be disabled.

Temperature Control

The controller compares the actual room tempe-

rature 

(P01)

  with  the  control  setpoint 

(P03)

  and 

activates the cooling relay which is able to switch 

solenoid  valves  or  compressors.  The  switching 

hysteresis (

P09

) prevents the system from short 

cycling. An idle time (

P11

) prevents a compressor 

from switching ON again immediately.
Setpoint range

With 

P07/P08

 you can limit the setpoint range to 

prevent the end-user from entering critical values.

Switching mode of cooling relay K1

The switching behavior of the cooling relay 

(= cooling mode) is defined by parameter 

P10

2. Setpoint / day-night-shift

 (1380-2 only)

To economize energy, e.g. at night, the unit can work 

with a second setpoint (

P04

), which can be activated 

by the internal time-switch (

P05/P06

). 

Emergency Mode of Temperature Control

If the control sensor fails, the unit starts an emer-

gency mode. 

The refrigeration relay switches on in 

a percentage rate of a total period of 30 minutes, 

preset by

 

P39

E.g.: selecting 40% means 12 minutes 

on, 18 minutes off.

ParNo.  Code 

Description 

Range 

 Default

P01

  ..................x .. x ...x ..x .. Actual temperature control sensor  (°C or °F) ......

display only

P02

  ..................x .. x ...x ..x .. Actual temp. evaporator sensor (°C or °F) ............

display only

P03

  ..... -- .........x .. x ...x ..x .. Setpoint .................................................................. Low limit P08...high limit P07 .................................................. 0 °C 

P04

   .... 88  ........... x ........x .. 2nd Setpoint (Night-Setpoint)  ............................... ± 100 °C (-148...212 °F)  ......................................................... 0

P05

   .... 88  ........... x ........x .. Start-up of night-setpoint (in 10 min. steps)  ......... 0...235, oFF  ............................................................................. oFF

P06

  ..... 88  ........... x ........x .. Stop of night-setpoint (in 10 minute steps)  .......... 0...235, oFF  ............................................................................. oFF

P07

  ..... 88 ........x .. x ...x ..x .. Highest adjustable setpoint  .................................. ± 100 °C (-148...212 °F) up to P08 ......................................... +50 °C

P08

  ..... 88 ........x .. x ...x ..x .. Lowest adjustable setpoint .................................... -100°C / -148°F up to P07 ....................................................... -50°C 

P09

  ..... 88 ........x .. x ...x ..x .. Setpoint hysteresis................................................. 0,0...20,0 K  .............................................................................. 2 K

P10

  ..... 88 ........x .. x ...x ..x .. Switching mode cooling relay ................................ 1= cooling, 2= heating  ............................................................ 1 

P11

  ..... 88 ........x .. x ...x ..x .. Cooling relay idle time ........................................... 0...59 minutes .......................................................................... 2 minutes 

P12

  ..... 88 ........x .. x ...x ..x .. Fan operation threshold ......................................... -100°C... +100°C (hyst. 3K fixed) ............................................ 50°C 

P13

  ..... 88 ........x .. x ...x ..x .. Fan operating mode .............................................. 1=, 2=, 3=, see text .................................................................. 1 

P14

  ..... 88 ........x .. x ...x ..x .. Fan delay after defrost ........................................... 0...30 minutes .......................................................................... 3 minutes 

P15

  ..................x .. x ...x ..x .. Remaining minutes till defrost ends ......................

display only

P16

  ..................x .. x ...x ..x .. Remaining minutes to activate cooling .................

display only

P17

  ..................x .. x ...x ..x .. Remaining minutes to start fan relay.....................

display only

P18

  ..................x .. x ...x ..x .. Remaining minutes up to an alarm .......................

display only

P19

  ..... 88 ........x .. x ...x ..x .. Calibration control sensor ...................................... +/-10,0 K/F ............................................................................... 0 K 

P20

  ..... 88 ........x .. x ...x ..x .. Calibration evap. sensor, resp. sensor OFF ...........+/-10,0 K/F, oFF ....................................................................... 0 K 

P21

  .....

70

  .......x .. x ...x ..x .. Sensor type / °C or °F / measuring range ............. 1= TF 501 / °C / -110...+120°C ................................................ 2    

 

 

         

2= TF 201 / °C / -55...+105°C

 

 

         

3= TF 501 / °F / -166...248°F

 

 

         

4= TF 201 / °F / -67...221°F

 

 

         

5= TF 202 / °C / -55...+105°C

 

 

         

6= TF 202 / °F / -67...221°F

P22

  ..... 88 ........x .. x ...x ..x .. Defrost termination temperature in °C or °F ......... 0,0...30,0°C / 118,0°F .............................................................. 10°C 

P23

  ..... 88 ............ x ........x .. Defrost type (independent from P10) .................... 1= electric, 2= hot gas, ............................................................ 1

 

 

         

3= eAZV, 4= hot gas+AZV (AZV with 1380-2 only)

P23

  ..... 88 ........x ........x ....... Defrost type (independent from P10) .................... 1= heater by cyclic timer, 2=hot gas by cyclic timer, ............... 1

 

 

         

3= heater by machine runtime, 4= hot gas by mach.runt.

P24

  ..... 88 ........x ........x ....... Defrost cycle .......................................................... 1...99 hours .............................................................................. 4 hours

P24

  ..... 88 ............ x ........x .. Defrost event # 1, 000...235, oFF ......................... (1.+.2 position = hours,  ........................................................... oFF 

P25

  ..... 88 ............ x ........x .. Defrost event # 2, 000...235, oFF ......................... 3.position = minutes x 10) ....................................................... oFF

P26

  ..... 88 ............ x ........x .. Defrost event # 3, 000...235, oFF ......................... " ................................................................................................ oFF

P27

  ..... 88 ............ x ........x .. Defrost event # 4, 000...235, oFF ......................... " ................................................................................................ oFF

P28

  ..... 88 ........x .. x ...x ..x .. Defrost safety operation time ................................ 0...120 minutes ........................................................................ 30 min. 

P29

  ..... 88 ........x .. x ...x ..x .. Drain time, refrigeration delay after defrost ........... 0...99 minutes .......................................................................... 0 min. 

P30

  ..... 88 ........x .. x ...x ..x .. Alarm Mode, Fan Relay Configuration .................. 0= Alarm relay active ON (N / O)............................................. 1  

 

 

x .. x ...x ..x ................................................................................... 1= Alarm relay active OFF (N / C)

 

 

 .........x ..x ................................................................................... 2= like "0", but internal beeper off 

 

 

 .........x ..x ................................................................................... 3= like "1", but internal beeper off 

 

 

x .. x ...x ..x ................................................................................... 4= Alarm relay resettable within alarm range (see text)

 

 

 ... x .............................................................................................. 5= Rel.4 switches with setpoint 2, alarm by LED only

 

 

 .........x ..x ................................................................................... 5= Alarm relay configured as fan relay ................................... 5

P31

  ..... 88 ........x .. x ...x ..x .. Alarm delay ............................................................ 1...99 minutes (if sensor fails < 1  flashing displ.) ......... 5 minutes 

P32

  ..... 88 ........x .. x ...x ..x .. Alarm high limit temperature (relative to P03) ...... 0...100 K  (0...100°F) ............................................................... 100K 

P33

  ..... 88 ........x .. x ...x ..x .. Alarm low limit (absolute value) ............................. ± 100 °C  (-148...212°F) .......................................................... -100°C 

P34

  ..... -- ............. x ........x .. Clock:  hours

P35

  ..... -- ............. x ........x .. Clock:  minutes

P36

  ..... -- ............. x ........x .. Clock:  seconds

P37

  ..... -- ............. x ........x .. Manual defrost ....................................................... "

"= Start defrost, "

"= Terminate

P38

  ..... 88 ........x .. x ...x ..x .. "Display Hold" (DH) while defrost event ................ 0 = OFF, 1 = ON ...................................................................... 0

P39

  ..... 88 ........x .. x ...x ..x .. ON-time of the control relay while sensor error 

 

 

        (Emergency Mode, based on 30 min. interval) ..... 0...100% ................................................................................... 50

P40

  ..................x .. x ...x ..x .. Current error + error listing .................................... Multiple errors present: Use "

/

" to read

P41

  ..... no ........x .. x ...x ..x .. Access Code .......................................................... 0...99......................................................................................... 0

Please note the different code for 

changing sensor type.

Default values are factory set.

1= cooling

2= heating

warm

activated

de-activated

cold

se

tpo

int

hys

ter

es

is

se

tpo

int

cold

hys

ter

esi

s

warm

de-activ.

activated

O N

30 minutes

Emergency Mode

in

 %

Cooling OFF

Cooling ON

O F F