Technical Manual Humidity Controller EVP 3260
Page 5
Assignment Page
(h)
Param.
Note
Range
Fact. Setting
h01
..........................Function of relay 1 ............................................
---
............................................................................................................
ALL
on
= continuous on
ALL
= alarm passive
ALK
= alarm active
toP
= dehumidify
bot
= humidification
h02
..........................Function of relay 2 ............................................ ditto. ............................................................................................................
toP
h03
..........................Function of relay 3 ............................................ ditto. ............................................................................................................
bot
h21
..........................Sensor function 1 .............................................
---
= off,
con
= control sensor (0...1000 Ohm) .......................................
---
h25
..........................Sensor function 5 .............................................
---
= off,
con
= control sensor (4...20mA) ..............................................
con
h26
..........................Sensor function 6 .............................................
---
= off,
con
= control sensor (0...10V) .................................................
---
h31
..........................Function of digital input (DI) 1 ..........................
---
= off, ...................................................................................................
---
dnL
= night operation (active low),
dnK
= night operation (active high)
ofl
= unit oFF (active low),
ofK
= unit oFF (active high)
tol
= dehumidifiy oFF (active low),
toK
= dehumidifiy oFF (active high)
bol
= humidification oFF (active low),
boK
= humidification oFF (active high)
P
ı
L
= PI control oFF (active low)
P
ı
K
= PI control oFF (active high)
h32
..........................Function of digital input (DI) 2 .......................... ditto. ..............................................................................................................
---
h40
..........................Analogue output delivers .................................
420
= current 4-20mA,
010
= voltage 0-10V ............................................
420
h41
..........................Analogue output works as/delivers ..................
---
= 0V / 4 mA .........................................................................................
---
100
= 100% (10V bzw. 20 mA),
d
ı
s
= actual value image
d
ıı
= actual value image, inverted
pt-
= PI controller dehumidify, at oFF 0%
pt-
= PI controller dehumidify, at oFF 100%
pb-
= PI controller humidification, at oFF 0%
pb-
= PI controller humidification, at oFF 100%
≤≥