Technical Manual Humidity Controller EVP 3260
Page 3
Error Messages / Error Memory / Error Codes
If a failure occurs, the controller will show parameter
L20
with a shortcut (see below) with a flashing
display automatically. If multiple errors are present, they can be called up by the up/down keys. Always
the last
15
error messages keep memorized with date and time of their appearance and can also be
read-out via data interface.
----
........no error
I
n
I
........the controller has been switched ON the first time or had data loss
hrd
......hardware failure
on
........mains voltage was switched ON (not a current but a historic failure)
off
......mains voltage was switched OFF (not a current but a historic failure)
t1
b
......sensor X broken
t5
b
......sensor X broken
t6
b
......sensor X broken
t5c
......sensor X hot-wired
A
H
I
.......alarm dehumidify
Alo
......alarm humidification
Adr
......network address assigned more than once
R
On
......Controller switch-on failure (not a current, but a historic failure)
R
OF
......Controller switch-off failure (not a current, but a historic failure)
sel
......Assignment failure
If a sensor is short or broken, a time delay of 5 seconds takes effect before an alarm will be activated.
Display of actual values and states
All actual values are shown on the "
Actual Values
Page
" (
(l)
).
State of the Controller Unit
If the 4 status LEDs
are blinking simul-
taneously and the display shows "oFF", the control
functions are disabled by digital input or data inter-
face.
Humidity Displays
"
L01, L05, L06
" (Actual Values Page) show the
actual values of the humidity sensors 1, 5 and 6 in
the range of 0...+100% r.H.. With "
P31, P35, P36
"
(Mode Page) this displays can be calibrated.
Setpoints
The active day or night setpoints are indicated by
the left decimal point switched on.
Time Information
The Actual Values Page contains all runtime-/
remaining time information, so the times up to the
start of a function can be read.
State of inputs/outputs
Digital-(DI)-Inputs State of the relays
Analogue Output: Parameter
L50
, value in %
Humidity Sensors from ELREHA
These types of Humidity Sensors can be used:
- FF 2520
, output 0...10V or 4...20mA
- FG xxx
, output 0...1000 ohms
The type of sensor can be set by '
h21, h25
and
h26
'
(Assignment Page).
Remote Display
The connection of remote displays of the TAA xx15
series is possible. This displays are able to show
optional the actual values of 'L01', 'L05' and 'L06'.
'Permanent Parameter' - Function
After power-up of the controller, the display will
indicate the 'permanent parameter' after some
seconds (or in case of a failure it will display the
current failure). This can also be read if you don’t
touch a key for more than 3 minutes. Factory set is
always the actual value of sensor 1.
If you think that it is suggestive to show any sensor
value as permanent parameter, do the following:
Change permanent parameter
- Select the parameter you want to have as
'permanent parameter'
- Press '
' and '
' simultaneously.
The display shows '
888
' for a moment, after
that the selected parameter will be shown as
the 'permanent parameter'.
Configuration Concept
The inputs/outputs of the EVP controller have no fixed
tasks. The EVP works with a "
free configurable
"
concept, this means that all available inputs and
outputs (
relays, digital inputs, analogue output
) can
be configured to work with any integrated control
function or control circuit.
Digital Inputs (DI, Optocoupler inputs)
Each digital input can be assigned to one of the
possible functions.
Relay Outputs
Each relay can be used to control one of the possible
functions. The same function can even be assigned
to multiple relays.
Parameter
Parameters of functions which are not assigned will not
appear in the parameter pages to improve survey.
Assignment
The function of each input and output can be preset
on the 'Assignment Page'. The assignment can be
done by keys or via interface.
Configuration of the controller
Hereby we use the example from above.
Action
Key
Display
Remarks
enter page listing .........................."
P
" ....... (A) ...............hold key for > 2 seconds
select assignment page................"
" .... (h)
enter asssignment page ..............."
P
" ....... h01 ..............h01 is the 1st parameter on the page and
determines the function of relay 1
displaying the function of relay 1 .."
P
" ....... any
new assignment of relay 1 ..........."
P
" ....... C00 ............(Code expected) only if no key key is hit for
about 3 minutes
enter access code ........................"
" ....... C88
confirm .........................................."
P
" ....... any
select function ..............................."
" .... toP ..............toP = control output dehumidify
confirm .........................................."
P
" ....... h01 ..............parameter # will be displayed again
select new in-/output ....................."
" ....... h02 ..............determines the function of relay 2
displaying the function of relay 2 .."
P
" ....... any
new assignment of relay 2 ..........."
P
" ....... any
select function ..............................."
" .... A1L .............A1L=alarm relay passive
confirm .........................................."
P
" ....... h02 ..............parameter # will be displayed again
Repeat this steps until all inputs and outputs are assigned to the desired functions.
1: - - -
1: con
1: - - -
dEF
dnh
sensor 1
relay 1
relay 2
relay 3
Analog
EVP
Assignment
In-/Outputs
toP
A1L
A2L
1
sensor 5
sensor 6
DI 1
DI 2
EVP
P
ELREH A
Configuration Example
Due to the free assignment, not all parameters
are required.
All not required parameters will be fade out.
DI
2
1
2
1
3
Relays
ON
OFF
mains
0V