ELREHA EVP 3260 Technical Manual Download Page 2

Technical Manual  Humidity Controller EVP 3260

Page 2

 Accessories

-  Humidity Sensor 

FF 2520 

or from the series 

FG xxx

-  PC-Software "

CV-Scheduler

"

-  Remote Displays of the 

TAA xx15 

series.

 Technical Data

Supply Voltage .............................230V 50-60Hz, max. 9VA (controller only), 

Ambient Temperature .......................................................................0...+50°C

Max. Ambient Humidity ..........................................85% r.H., not condensing
Inputs ........ 3x Humidity Sensor: 1x  0...1000 Ohm, 1x 4...20mA, 1x 0...10V 

Accuracy   .................................for the ambient temperature range 10..30°C 

 

 

Standard signal inputs ±2%

 

 

0...1000 ohm input: 

 

 

from 0-200 Ohm ±5% , 

 

 

from 200-500 Ohm ±2%, 

 

 

from 500-1000 Ohm ±1% 

 

 

Sensor broken from >= 1200 Ohm

Display Resolution ......................................................1% or 0,1% switchable

Digital Inputs ..................................................................2x 230V~, max. 3mA

 

overvoltage category II, pollution degree 2

Relay Outputs .................. 1x SPDT, 2x SPST, isolated, 8A res/3A ind./250V 

 

overvoltage category III, pollution degree 2

Voltage Supply for Humidity Sensor ..................22V DC ±10%, 40 mA max.

Analogue Output ............................................ 0...10V or 4...20mA switchable

 

0...10 VDC, max. current typ. 1mA  

 

4...20 mA, max. shunt resistance 250 ohms

Display/Parameter Ranges .......................................... see parameter pages

Interfaces ........................................................................................2x RS 485

Data Storage ......................................................................................unlimited

Real Time Clock .........................................automatic summer/winter switch, 

 

10 days clock backup without mains voltage

Housing ................plastic with foil keypad for rail mounting (DIN EN 50022),

 

screw terminals 2,5 mm²

 CONNECTION INFORMATION & SAFETY INSTRUCTIONS

The guarantee will lapse in case of damage caused by failure to 

comply with these operating instructions! We shall not be liable 

for any consequent loss! We do not accept liability for personal 

injury or damage to property caused by inadequate handling 

or non-observance of the safety instructions! The guarantee 

will lapse in such cases.

This manual contains additional safety instructions in the func-

tional description. Please note them!
If you notice any damage, the product may not be connected

to mains voltage! Danger of Life!

A riskless operation is impossible if:

• The device has visible damages or doesn't work

• After a long-time storage under unfavourable conditions

• The device is strongly draggled or wet

• After inadequate shipping conditions
• Never use this product in equipment or systems that are  

  intended to be used under such circumstances that may  

  affect human life. For applications requiring extremely  

  high reliability, please contact the manufacturer first.
• 

The product may only be used for the applications  

  described on page 1.
•  Electrical installation and putting into service must be  

  done from qualified personnel. 

• 

 During installation and wiring never work when the 

  electricity is not cut-off ! Danger of electric shock!

• 

 Never operate unit without housing. 

  Danger of electric shock!

•  

All ‘PE’ terminals must be connected to ground.  

  Danger of electric shock! 

Without PE the internal noise  

  filter will not work, faulty indicated values may occur.
•  Please note the safety instructions and standards of your  

  place of installation!
•  Before installation: Check the limits of the controller and  

  the application (see tech. data). Check amongst others:

  - Make sure that all wiring has been made in accordance  

    with the wiring diagram in this manual.

  - Supply voltage (is printed on the type label).

  - Environmental limits for temperature/humidity. 

  -  Maximum admitted current rate for the relays. Compare  

    it with the peak start-up currents of the controlled loads 

    (motors, heaters,etc.). 

 

  Outside these limits malfunction or damages may occur.
•  Sensor/probe cables must be shielded. Don’t install them  

  in parallel to high-current cables. Shielding must be  

  connected to PE at the end close to the controller. 

  If not, inductive interferences may occur. 
•  Please note for elongation: The wire gauge is not critical,  

  but should have 0,5mm² as a minimum.
•  Mounting the controller close to power relays is    

  unfavourable. Strong electro-magnetic interference,  

  malfunction may occur!
•  Take care that the wiring of interface lines meets the  

  necessary requirements.

Cleaning

 

The use of a dry, lint-free cloth is sufficient to clean the product. 

Never use liquids or acidic fluids!  Risk of damage!

Danger

Notice

Caution

Notice

Summary of Contents for EVP 3260

Page 1: ...int Page P Mode Page h Assign ment Page L01 r01 P01 h01 1 Parameter on the P P P Access Protection Except the temperature setpoints parameters can be changed only after entering a correct access code...

Page 2: ...After a long time storage under unfavourable conditions The device is strongly draggled or wet After inadequate shipping conditions Never use this product in equipment or systems that are intended to...

Page 3: ...the controller the display will indicate the permanent parameter after some seconds or in case of a failure it will display the current failure This can also be read if you don t touch a key for more...

Page 4: ...oFF switched off from the VPR 0 1 off L43 X Day Night Mode 0 day 1 night 0 1 L44 X Operation state of the controller on off L50 X Current value of the analogue output in X of the selected range 0 100...

Page 5: ...ht operation active low dnK night operation active high ofl unit oFF active low ofK unit oFF active high tol dehumidifiy oFF active low toK dehumidifiy oFF active high bol humidification oFF active lo...

Page 6: ...resis humidification Setpoint dehumidify Setpoint humidification Night setpoint dehumidify Night setpoint humidification Setpoint dehumidify Hysteresis dehumidify 100 0 Setpoint humidification Hystere...

Page 7: ...ity Dimensions Connection 1 2 3 4 1 2 8 3 4 5 7 6 12 11 9 13 10 22 EVP 20 21 27 23 24 25 26 28 32 29 31 30 105 4 13 46 1 81 63 2 48 91 3 58 115 4 53 19 15 18 14 16 17 ELREHA P 38 37 34 33 35 36 analog...

Reviews: