background image

Technical Manual   Cold Storage Controller EVP 3150-1 and EVP 3150-2

Page  7

 Cooling

Cooling control by Solenoid Valve / Compressor

Cooling is controlled by switching the output relay 

contacts ON an OFF. 

For freezing applications, the N/C contact can be 

used (inverted mode) to secure permanent cooling 

in case of a controller defect, adjustable by "

P03

"

 

(Mode Page). 

The point of cut-off is always the valid setpoint. If the 

temperature at the control sensor exceeds setpoint 

+

 hysteresis ("

r10

"

Setpoint Page)

,

 the control relay 

will switch on. "

P03

"

 

also affects to the switching 

characteristic of the fan relay. 

Do not use 'inverted', if compressors are 

controlled  directly.  Risk  of  compressor 

damage by continuous running!

The control relay can be locked via data interface.

Low temperature Limitation

Can be used e.g. for refrigerated shelfs with roller 

blinds to limit the temperature at the air outlet during 

night operation. When the temperature at the alarm 

sensor decreases the limit set by "

r43

" (resp. "

r44

"

,

 

Setpoint Page) cooling will switch off.  

This value is the threshold for the low temperature 

alarm at the same time. 

The low temperature limitation cannot be 

switched off.

 Runtime Monitoring

The controller monitors the total running hours of 

the cooling output over 3 days. A 'day' is defined 

as the period within "

P42

" and 1 minute before the 

same point in time next day.

Example

:

"

P42

" set to 11:00 am =

Monitoring time range is from 11:00 o'clock day 1up 

to 10:59 o'clock day 2.

The overall runtime of the cooling relay over a day 

will  be  added  and  stored  ("

L21

",  Actual  Values 

Page). If this runtime exceeds the value set by "

r31

three days in a sequence, this will cause an alarm 

at the hour programmed by "

P42

" (Mode Page). 

The alarm relay will be de-activated and the alarm 

LED switches on.

This  alarm  will  be  cancelled  automatically  1 

hour later. 

 Operation with a single compressor

If a single compressor is controlled by a refrigeration 

relay, it is suggestive to have an idle time to prevent 

the machine from damages caused by short cycle 

operation. The compressor can restart only after the 

timer "

r33

" (Setpoint Page) has been run down. The 

remaining time up a restart can be read at "

L36

(Actual Values Page).

 Temperature Alarm

If a relay gets the function "ALA", a temperature alarm 

will be forwarded by the 'Quiescent current' principle. 

After power-up of the controller, the alarm relay will 

be energized after ~4 sec. In case of a failure the 

relay will be de-energized after a delay timer (

"

r45

", 

Setpoint  Page)  has 

been run down. LED 

"Alarm"  shows  the 

alarm state. If tempe-

rature comes back to 

the normal range, the 

relay will be energized 

again.  "

L32

"  shows 

the remaining time up 

to an alarm. 

Overtemperature Alarm

It is possible to select max. 4 (5 with the 'virtual') alarm 

sensors (e.g. 4x "

ALA

"). If the temperature at one of 

the alarm sensors exceeds the control se the 

"

r41

" (resp. "

r42

", Setpoint Page) setting, an alarm 

will be initiated after the delay time "

r45

".

Low temperature Alarm

If the temperature at any alarm sensor gets lower 

than the  "

r43

" (resp. "

r44

"

,

 Setpoint Page) setting, 

an  alarm  will  come  on  with  the  delay  explained 

above. This setting is an absolute value and does 

not refer to the control setpoint. At the same time, this 

setting works as threshold for the "low temperature 

limitation" function. 

Low temperature alarm can be disabled by "

P41

(Mode Page).

Supplementary alarm delay during defrost

After a defrost cycle the temperature may take longer 

to stabilize and the normal alarm delay turns out to 

be too short. For this reason the value of parameter 

d33

“ (defrost page) will be added on to the normal 

alarm delay after defrosting. 

cooling relay normal

cooling relay inverted

 Heating function

One relay is able to work as a heat relay. Then the 

control setpoint is the cut-off of heating and cooling 

at the same time. Cut-in will be:

• 

for cooling: 

se hysteresis (r10)

  for heating: 

setpoint - hysteresis (r10).

 'Physical' and 'virtual' sensors

1. Each 'physical' (real) sensor is able to fulfill up to 3 

functions at the same time (see Assignment Page), 

any sensor is able to do the same job. 

Up to 4 control sensors can be assigned the same 

time. If 

one of them

 gets warmer than se 

hysteresis, then cooling starts. 

2. It is possible to create a 'virtual' sensor to realize 

different kinds of averaging, e.g. multiple sensors in 

a huge room or averaging of inlet and outlet sensor in 

a chest freezer. The 'virtual' sensor resp. value (

L07

follows from the selectable emphasis of the sensors 

which must have an effect on the result (

h17, h27, 

h37, h47

, Assignment Page). The functions assigned 

to this 'sensors' (

h71, h72, h73

, Assignment Page) 

are the same as the functions for the 'physical' sen-

sors. 

Example

: If the 'physical' sensor 1 got the function 

"

con

" (control sensor) and also the 'virtual' sensor, 

then the warmer one initiates refrigeration.

-  Selection of a "virtual sensor":

  -  Assignment of a function by 

h71-h73 

-  Selection of a 'physical' sensor which must have  

  an effect on the result :

  -  Activating of the sensor by assigning a 

    function (e.g. display only sensor)

-  Set emphasis for the selected sensor

  (

h17, h27, h37, h47

).

The  sum  of  all  emphasis  values  must  be 

100%. 

Example

If sensor 1 and sensor 2 must have an effect 

on the result and you set "

h17

" to "30%" and 

"

h27

" to "60%", then you get the error message "

SEL

(assignment error).

Further causes for the error message "

SEL

"

-   The sum of all emphasis parameters is 100%,  

  but no virtual sensor function is selected

-   All 4 emphasis values are set to '0' and  a  

  'virtual' sensor function is assigned

-   A physical sensor is switched off, but an   

  emphasis value > 0 is selected. 

Example 1, Chest Freezer:

For the detection of the actual value, inlet and outlet 

sensor must be used. Sensor 1 is mounted at the 

suction side (inlet) and must have an 60% influence 

on the result. Sensor 2 is mounted at the outlet and 

must have an 40% influence.

-  set "

h17

" to "60"

-  set "

h27

" to "40"

-  set "

h71

" to "con" (control sensor)

Example 2, huge room, standard application

Sensors 1-3 must measure the rooms temperature, 

an arithmetic average must be calculated, sensor 4 is 

the defrost limitation sensor in the evaporator.

-  set "

h17

", "

h27

" to "33" and "

h37

" to "34"

-  set "

h71

" to "con" (control sensor)

-  set "

h41

" to "df1"

Special Function

If an emphasis parameter value is set to 

100% (others to 0), up to 6 functions can 

be assigned to the corresponding physical sensor. 

This may be of interest for applications where 

more than 3 sensor functions are used.

M

L

M

L

cooling

fan

cooling

fan

P03 set to 'nor'

P03 set to 'in'

active-

passive

phase

cooling = relay on

relay on

freezing=

relay off

cold

warm

warm

cold

setpoint

setpoint

Hysteresis

Hysteresis

relay off

refrig. on

Heizen ein

cold

warm

off

setpoint

Hysteresis

Hysteresis

Summary of Contents for EVP 3150-1

Page 1: ...ming Enter access code if necessary Change value If you hold the key the values change faster and faster P Confirm programming P 2 sec Page name will be displayed again If an older version must be replaced please note the modified terminals Technical Manual 5311092 00 26E Cold Storage Controller from SoftVers 1 61 Types EVP 3150 1 EVP 3150 2 ELEKTRONISCHE REGELUNGEN GMBH Please note safety instruc...

Page 2: ...personal injury or damage to property caused by inadequate handling or non observance of the safety instructions The guarantee will lapse in such cases This manual contains additional safety instructions in the functional description Please note them If you notice any damage the product may not be connected to mains voltage Danger of Life A riskless operation is impossible if The device has visibl...

Page 3: ...01 is the 1st parameter on the page and determines the function of relay 1 displaying the function of relay 1 P any new assignment of relay 1 P C00 Code expected only if no key key is hit for about 3 minutes enter access code C88 confirm P any select function ALA ALA alarm relay confirm P h01 parameter will be displayed again select new in output h02 determines the function of relay 2 displaying t...

Page 4: ...s 02 0 48 0 h min 24 0 h d11 Defrost release time 1 in 10 minutes steps 00 0 23 5 off 05 0 d12 Defrost release time 2 in 10 minutes steps 00 0 23 5 off off d13 Defrost release time 3 in 10 minutes steps 00 0 23 5 off off d14 Defrost release time 4 in 10 minutes steps 00 0 23 5 off off d15 Defrost release time 5 in 10 minutes steps 00 0 23 5 off off d16 Defrost release time 6 in 10 minutes steps 00...

Page 5: ...ve Control 1 999 sec 240 sec P65 Superheat maximum value 2 0 100 0K 8 0K P66 Limitation of EEx valve signal 0 100 100 P67 Actuating Variable Delay EEx valve step size 1 100 100 P68 Actuating Variable Delay EEx valve output delay 0 240 sec 0 P79 X Software version P81 Standard of summer winter switch oFF on EU since 96 on P82 P83 Year Month P84 P85 Day Hour P86 P87 Minute Second P90 Address of the ...

Page 6: ...y digital input or via interface LED on defrost increase values decrease values this setpoint is active Connection EVP 3150 1 Older product production discontinued DI 1 relay K2 10 29 analog out EVP 3150 1 24V supply L DI 2 mains 2 1 N 3 L 4 N 7 6 5 8 9 relay K1 24 21 20 22 23 NDO DO RS 485 26 25 28 27 sensor 3 sensor 4 sensor 1 sensor 2 0 10V IN 15 SSR K4 230V AC 11 12 14 13 relay K3 18 L 230V AC...

Page 7: ...eshold for the low temperature limitation function Low temperature alarm can be disabled by P41 Mode Page Supplementary alarm delay during defrost Afteradefrostcyclethetemperaturemaytakelonger to stabilize and the normal alarm delay turns out to be too short For this reason the value of parameter d33 defrost page will be added on to the normal alarm delay after defrosting cooling relay normal cool...

Page 8: ...ller OFF If a digital input is assigned to the functions oFL or oFH and is activated by the matching signal then all control functions will be disabled All alarm functions are locked and the display shows oFF Safety Chain Monitoring When using the controller for single compressor appli ca tions one of the digital inputs can be used to monitor the safety chain chA Normally the digital input is conn...

Page 9: ...he superheat value is determined by P60 only Function is disabled P65 Superheat maximum value exceeds P60 Function enabled P65 is below or equal to P60 Temperature control with Electronic Expansion Valves Sensor Positions Pressure Transmitter Temperatur Sensor method 2 Temperature Sensors method Parameterization Thefollowingrecommendationsrefertothepressure transmitter DG 1 9 2 10V L05 Display of ...

Page 10: ...tion where by experience iceremainsthelongesttime Ifthetemperaturerises at that position the ice in the evaporator is probably melted completely Adefrost cycle is completed as soon as the defrost sensor has reached the defrost limitation tempera ture d31 Defrost Page If 2 defrost sensors are assigned both sensors must achieve the limitation temperature to termi nate defrost Defrost termination by ...

Page 11: ...influence If you want to prevent that defrost starts at certain day times use all the defrost release times and set them to points in time where defrost is allowed If no icing is detected these times will be ignored On the other hand once icing detected the controller will wait for the next defrost release time before starting a defrost cycle External command Assign one of the digital inputs to de...

Page 12: ...al input OK DI1 is configured at h61 to the value AnA r63 is set to 50 If the analogue output works as voltage output it delivers 5V DC If it works as current output it delivers 12 mA Electronic Expansion Valves with analogue input The analogue output is able to control expansion valves with analog input Therefore h52 must be set to EEP Also in this case h51 serves as a switch for a voltage or cur...

Page 13: ...o 0 2 fan interval mode defrost by fan A relay is reserved for fan control P02 is set to Int d01 is set to on 3 fan interval mode defrost by electric heater hot gaz A relay is reserved for fan control P02 is set to Int d01 is set to oFF The fan runs while cooling is on will be disabled during defrost periods and comes on after defrost with a time delay set by parameter r22 4 fan in permanent mode ...

Page 14: ...fthe ambient air market temperature The information about current market temperature and humidity the controller gets from a superior system VPR 5240 can also be disabled ther to calculate the absolute humidty Ifoneoftherelaysisassignedto FrA thiswillcontrol theframeheaterenergywithacertainfrequencyand pulse width For day and night operation you can choose different values to save energy The corre...

Page 15: ...ry for selecting the right controller when a data package is transmitted on the network bus If the controller is used outside a network these parameters are of no importance Remote control at Frontend Systems EVP controllers can be operated remotely via interface when they are connected to Frontend Systems such as SMZ or VPR Inthiscase theFrontendSystemshowstheEVP s display contents and the keys o...

Page 16: ...the minimum specifications of the used pressure transmitter In practise up to 10 controllers mostly work trouble free Sensor positions for EEx Valve control Temperature Sensors Method alternative positions for Outlet Sensor Please care for a good isolation by foamed material so that none of the sensors get contact with the airflow Pipe mounting Most expedient is it to use cable fixers some thermal...

Reviews: