Technical Manual   Cold Storage Controller EVP 3150-1 and EVP 3150-2

Page 10

The EVP allows several, different defrost methods. 

Up to 3 defrost relays can be assigned. This relay 

output(s) then control an electric heater or fan which 

defrost the evaporator(s). 

Each evaporator with electric heater is monitored 

by a defrost termination sensor.

According to the application, the fan can stop or run 

during the defrost cycle. 

 

"

d02

" (Defrost Page) fixes the defrost initiation  

  mode. 
  - "

Etn

" :  Defrost is initiated by a digital input

  - "

Int

"

 

:   Defrost can be initiated by digital  

   

input or the internal time-switch.

  - "

AdA

": Defrost is controlled by the intelligent  

   

(adaptive) defrost algorithm

Electric defrost heaters are always switched by the 

N/O contact of the defrost relay. "

L33

" shows the 

remaining time up to the end of the defrost cycle.

Defrost release by internal timer

With parameters "

d11

"..."

d16

" (Defrost Page) you 

set  six  (6)  possible  defrost  release  times.  This 

points-in-time can be set in 10 minute steps only, 

that means a defrost time like 6:55 is impossible. 

Times on the display:

The precondition for the start of a defrost cycle is 

that at least one of the defrost termination sensors 

detects a temperature below limitation temperature. 

If parameter

 

"

d02

" is set to "

Etn

" (external only), a 

defrost cycle cannot be initiated by the timer.

 

Please note that this function differs  

 

with the 'adaptive' defrost method

External (Remote) Defrost Initiation 

To start de-icing by a digital input, note that mains 

phase has to be applied for 2 seconds minimum 

and  last  not  longer  than  the  shortest  possible 

defrost cycle. 

Break before defrost

Parameter ‘

d38

’ (defrost page) effects a delayed 

energizing of the heater at the beginning of the 

defrost cycle. By this, the rest of the evaporators 

chillness can be blown to the storage. 

The defrost heaters must deliver less energy, 

because the evaporator is already warmed up.

Defrost termination by temperature

The EVP controller is able to work with up to 3 defrost 

relays (= evaporators). Defrost is individually temi-

nated for each defrost output  by the corresponding 

defrost (evaporator) sensor. This evaporator sensor 

must be placed at a position where, by experience, 

ice remains the longest time. If the temperature rises 

at that position, the ice in the evaporator is probably 

melted completely. 

A defrost cycle is completed as soon as the defrost 

sensor has reached the defrost limitation tempera-

ture "

d31

" (Defrost Page).

If  2  defrost  sensors  are  assigned,  both  sensors 

must achieve the limitation temperature to termi-
nate defrost.

Defrost termination by time

If no defrost sensors are assigned or if they are out 

of order, the defrost cycle will be terminated after 

"

d32

" (Defrost Page) has been run down. "

L33

shows the remaining time up to termination.

Defrost termination time monitoring

The unit captures the number of defrost cyles which 

are terminated by time (min. 1 defrost term. sensor 

must be assigned). If the number of defrost cycles 

terminated by time exceed the number programmed 

by  "

d37

"  (Defrost  Page)  an  alarm  message  will 

be generated. With this function, massive icing or 

defective defrost heaters can be recognized timely 

and reliable.

In case of airflow-defrost without evapora-

tor sensor, this function must be disabled 

("

oFF

"), because here every defrost will be 

terminated by timer and no alarm message 

is desired.

Cooling Delay (drain time)

After defrost is terminated, the solenoid valve keeps 

locked for the time set by "

d35

" (Defrost Page). 

"

L34

" shows the remaining time up to the restart 

of cooling.

Manual Defrost

A manual defrost initiation is possible at any time. 

To start manual defrost:

  Select "

d50

" (Defrost Page), 

  set it to "

on

" and confirm. 

Stop manual defrost

  Select "

d50

" (Defrost Page), 

  set it to "

oFF

" and confirm. 

3rd position =

Minutes  x  10,  that 

means  no  single 

minutes  will  be  dis-

played

1st/ 2nd position = 

hours

Pulsed Defrost 

To save energy it’s possible to work with a pulsed 

(switched in intervals) defrost function. 

If the evaporator temperature is located within "

d34

(Defrost Page) and the limitation temperature "

d31

(the value of "

d34

" must be lower than limitation 

temperature), the controller determines about the 

optimal heat distribution in the evaporator depending 

on the gradients of the temperature. The heater will 

be switched on in controlled periods until the defrost 

limitation temperature is reached.
The result of this procedure:

  Heat energy in the evaporator will be distributed  

  much better

  Defrost limitation temperature can be set to a  

  lower value

  Less of humidity in the chamber

  Save of energy

 Defrost

Summary of Contents for EVP 3150-1

Page 1: ...ming Enter access code if necessary Change value If you hold the key the values change faster and faster P Confirm programming P 2 sec Page name will be displayed again If an older version must be replaced please note the modified terminals Technical Manual 5311092 00 26E Cold Storage Controller from SoftVers 1 61 Types EVP 3150 1 EVP 3150 2 ELEKTRONISCHE REGELUNGEN GMBH Please note safety instruc...

Page 2: ...personal injury or damage to property caused by inadequate handling or non observance of the safety instructions The guarantee will lapse in such cases This manual contains additional safety instructions in the functional description Please note them If you notice any damage the product may not be connected to mains voltage Danger of Life A riskless operation is impossible if The device has visibl...

Page 3: ...01 is the 1st parameter on the page and determines the function of relay 1 displaying the function of relay 1 P any new assignment of relay 1 P C00 Code expected only if no key key is hit for about 3 minutes enter access code C88 confirm P any select function ALA ALA alarm relay confirm P h01 parameter will be displayed again select new in output h02 determines the function of relay 2 displaying t...

Page 4: ...s 02 0 48 0 h min 24 0 h d11 Defrost release time 1 in 10 minutes steps 00 0 23 5 off 05 0 d12 Defrost release time 2 in 10 minutes steps 00 0 23 5 off off d13 Defrost release time 3 in 10 minutes steps 00 0 23 5 off off d14 Defrost release time 4 in 10 minutes steps 00 0 23 5 off off d15 Defrost release time 5 in 10 minutes steps 00 0 23 5 off off d16 Defrost release time 6 in 10 minutes steps 00...

Page 5: ...ve Control 1 999 sec 240 sec P65 Superheat maximum value 2 0 100 0K 8 0K P66 Limitation of EEx valve signal 0 100 100 P67 Actuating Variable Delay EEx valve step size 1 100 100 P68 Actuating Variable Delay EEx valve output delay 0 240 sec 0 P79 X Software version P81 Standard of summer winter switch oFF on EU since 96 on P82 P83 Year Month P84 P85 Day Hour P86 P87 Minute Second P90 Address of the ...

Page 6: ...y digital input or via interface LED on defrost increase values decrease values this setpoint is active Connection EVP 3150 1 Older product production discontinued DI 1 relay K2 10 29 analog out EVP 3150 1 24V supply L DI 2 mains 2 1 N 3 L 4 N 7 6 5 8 9 relay K1 24 21 20 22 23 NDO DO RS 485 26 25 28 27 sensor 3 sensor 4 sensor 1 sensor 2 0 10V IN 15 SSR K4 230V AC 11 12 14 13 relay K3 18 L 230V AC...

Page 7: ...eshold for the low temperature limitation function Low temperature alarm can be disabled by P41 Mode Page Supplementary alarm delay during defrost Afteradefrostcyclethetemperaturemaytakelonger to stabilize and the normal alarm delay turns out to be too short For this reason the value of parameter d33 defrost page will be added on to the normal alarm delay after defrosting cooling relay normal cool...

Page 8: ...ller OFF If a digital input is assigned to the functions oFL or oFH and is activated by the matching signal then all control functions will be disabled All alarm functions are locked and the display shows oFF Safety Chain Monitoring When using the controller for single compressor appli ca tions one of the digital inputs can be used to monitor the safety chain chA Normally the digital input is conn...

Page 9: ...he superheat value is determined by P60 only Function is disabled P65 Superheat maximum value exceeds P60 Function enabled P65 is below or equal to P60 Temperature control with Electronic Expansion Valves Sensor Positions Pressure Transmitter Temperatur Sensor method 2 Temperature Sensors method Parameterization Thefollowingrecommendationsrefertothepressure transmitter DG 1 9 2 10V L05 Display of ...

Page 10: ...tion where by experience iceremainsthelongesttime Ifthetemperaturerises at that position the ice in the evaporator is probably melted completely Adefrost cycle is completed as soon as the defrost sensor has reached the defrost limitation tempera ture d31 Defrost Page If 2 defrost sensors are assigned both sensors must achieve the limitation temperature to termi nate defrost Defrost termination by ...

Page 11: ...influence If you want to prevent that defrost starts at certain day times use all the defrost release times and set them to points in time where defrost is allowed If no icing is detected these times will be ignored On the other hand once icing detected the controller will wait for the next defrost release time before starting a defrost cycle External command Assign one of the digital inputs to de...

Page 12: ...al input OK DI1 is configured at h61 to the value AnA r63 is set to 50 If the analogue output works as voltage output it delivers 5V DC If it works as current output it delivers 12 mA Electronic Expansion Valves with analogue input The analogue output is able to control expansion valves with analog input Therefore h52 must be set to EEP Also in this case h51 serves as a switch for a voltage or cur...

Page 13: ...o 0 2 fan interval mode defrost by fan A relay is reserved for fan control P02 is set to Int d01 is set to on 3 fan interval mode defrost by electric heater hot gaz A relay is reserved for fan control P02 is set to Int d01 is set to oFF The fan runs while cooling is on will be disabled during defrost periods and comes on after defrost with a time delay set by parameter r22 4 fan in permanent mode ...

Page 14: ...fthe ambient air market temperature The information about current market temperature and humidity the controller gets from a superior system VPR 5240 can also be disabled ther to calculate the absolute humidty Ifoneoftherelaysisassignedto FrA thiswillcontrol theframeheaterenergywithacertainfrequencyand pulse width For day and night operation you can choose different values to save energy The corre...

Page 15: ...ry for selecting the right controller when a data package is transmitted on the network bus If the controller is used outside a network these parameters are of no importance Remote control at Frontend Systems EVP controllers can be operated remotely via interface when they are connected to Frontend Systems such as SMZ or VPR Inthiscase theFrontendSystemshowstheEVP s display contents and the keys o...

Page 16: ...the minimum specifications of the used pressure transmitter In practise up to 10 controllers mostly work trouble free Sensor positions for EEx Valve control Temperature Sensors Method alternative positions for Outlet Sensor Please care for a good isolation by foamed material so that none of the sensors get contact with the airflow Pipe mounting Most expedient is it to use cable fixers some thermal...

Reviews: