48
User Manual
MN032EN
Effective October 2017
215U-2 802.11
wireless I/O and gateway
EATON
www.eaton.com
I/O store for 115S-12 expansion I/O modules
I/O store
Description
0001 + Offset
0008 + Offset
DIO outputs 1–8
10001 + Offset
10008 + Offset
DIO Inputs 1–8
10019 + Offset
Modbus Error indication for 115S module
10020 + Offset
Detected indication for this 115S module
30001 + Offset
30008 + Offset
Inputs AIN 1–AIN 8
30017 + Offset
Modbus Error counter for this 115S module
30018 + Offset
Modbus Last Error code for this 115S module (see “Expansion I/O error registers” on
page 35
)
30019 + Offset
Modbus Lost Link counter for this 115S module
30020 + Offset
Module type (0x0201) = 513/error status
40009 + Offset
40016 + Offset
Pulsed output target 1–8 (1 register per output)
I/O store for 115S-13 expansion I/O modules
I/O store
Description
0001 + Offset
0008 + Offset
DIO outputs 1–8
10001 + Offset
10008 + Offset
DIO inputs 1–8
10019 + Offset
Modbus Error indication for 115S module
10020 + Offset
Detected indication for this 115S module
30017 + Offset
Modbus Error counter for this 115S module
30018 + Offset
Modbus Last Error code for this 115S module (see “Expansion I/O error registers” on
page 35
)
30019 + Offset
Modbus Lost Link counter for this 115S module
30020 + Offset
Module type (0x0301) = 769/error status
40001 + Offset
40008 + Offset
Analog output 1–8
40009 + Offset
40016 + Offset
Pulsed output target 1–8 (one register per pulsed output)
Physical I/O registers
I/O
Input
Output
Digital I/O 1
10001
1
Digital I/O 2
10002
2
Digital I/O 3
10003
3
Digital I/O 4
10004
4
Digital I/O 5
10005
5
Digital I/O 6
10006
6
Digital I/O 7
10007
7
Digital I/O 8
10008
8
Analog Input 1 (mA)
30001
—
Analog Input 2 (mA)
30002
—
Analog Input 3 (mA)
30003
—
Analog Input 4 (mA)
30004
—
Input 5 – Local V Supply
30005
—
Input 6 – Local +24 V Analog Loop
30006
—
Input 7 – Local V Battery
30007
—
Input 8 – Local V Expansion I/O
30008
—
Analog Input 1 (Volts)
30009
—
Analog Input 2 (Volts)
30010
—
Analog Input 3 (Volts)
30011
—