BIOTOPUS II
- Operator manual
Page 67
EXTERNAL INPUT
The RESCUE SYSTEM permit the connection of two separate ON-OFF switches (sensors)
that can be used to sense, for example, a level, the presence of water on the fl oor, the
opening of a door etc. etc. These switches must be “NORMALLY CLOSED”. When one of
these contact is open, an ALARM SMS will be sent thorugh the BIO-LINK SMS.
Note:
1) an SMS will be sent at the end of the BLACK OUT
2) in the BLACK-OUT is shorter than 15 minutes, no SMS will be sent
3) the pump(s) will start cycling after 20 minutes from the BLACK-OUT
4) at 24:00 the pump will run for 5 sec to perform an “autocleaning” procedure
5) the Back -up battery is constantly keeped charged by the RESCUE SYSTEM
6) the opening of one (or both) of the two optional contacts will generate the alarm
after 20 sec. from the alarm condition (opening of the contact)