background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200574_01K May  2016                       ©2016 ELMDENE INTERNATIONAL LTD  

 

O

PERATING 

I

NSTRUCTIONS

 

 

 
In the event of loss of mains, a battery fault or a GEN fault, the corresponding Fault signal contacts will open.  
 
If the output of the PSU fails, the cause of the failure should be investigated e.g. short circuit load, 
connection of a deeply discharged battery. The fault should be rectified before restoring power to the PSU. If 
any of the fuses require replacing, ensure the correct fuse rating and type is used. 
 

M

AINTENANCE

   

 

Maintenance 

This unit is intended for use by Service Personnel only.  There are NO USER SERVICEABLE parts inside. 
 
There is no regular maintenance required of the PSU other than periodic testing, and replacement of the 
standby battery.  

Reference should be made to the battery manufacturer's documentation to determine 

typical/expected battery life with a view to periodic replacement of the battery.  

 
 

 

D

IAGNOSTICS

 

 

 
Local Diagnostics 

Green LED 

On = Mains Present 

Yellow LED 

Fault Diagnostics according to table: 

 

Yellow LED 

(fault) 

Green LED 

(mains) 

Status 

OFF 

ON 

Normal:

  Battery fully charged 

One short flash 

every second 

ON 

Normal:

  Battery charging but not fully charged 

Flashing: 

1second On 

1 second Off 

ON 

Fault:

  Output fuse or battery fuse blown, or 

battery missing 

OFF 

Fault:

  No mains, output fuse blown 

One short flash 

every 3 seconds 

OFF 

Fault:

  No mains, battery supplying load. 

OFF 

OFF 

Fault:

  No mains, No output, Batteries 

disconnected or completely discharged 

 
 

Summary of Contents for BATT-BOX-65

Page 1: ...volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fau...

Page 2: ...A 7 5 A 10 0 A 7 2 A 6 5 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12 V PS12170 NP17 12 BS131N 2 x 38 Ah 12 V PS12380 NP38 12 2 x 65 Ah 12 V PS12650 NP65 12 BS13...

Page 3: ...N Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN...

Page 4: ...e monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detecte...

Page 5: ...signed to support two 17 or 18 Ah batteries and as such weighs a total of 19 5 Kg when loaded Ensure that wall fixings are appropriate to support this weight 6 The product should be mounted no further...

Page 6: ...ed by conduit if it is being used to power the CIE directly 16 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through...

Page 7: ...ling 4 Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault monitoring is required Figure 4 Power Load and Battery connections 5 Connect the load output...

Page 8: ...4 5 14 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 5 15 If the batteries are housed remotely replace the battery lead assembly including battery te...

Page 9: ...arts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation...

Page 10: ...sposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal rou...

Reviews: