background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200574_01K May  2016                       ©2016 ELMDENE INTERNATIONAL LTD  

Where the PSU Fault and EPS Fault outputs are used, they should only be connected to circuits having voltages less 
than 60 Vdc. 

 

Cable Sizing

 

1)

 

Mains input cable must be to the applicable standard with a 5 A or greater current capacity, i.e. 0.75 mm

2

 

nominal conductor area, having a minimum operating voltage of 300/500 Vac. 

2)

 

The low voltage output cable must be sized to carry the rated load current to the devices connected to the 
PSU. 

3)

 

Mains input and low voltage output cables should be routed to use different entry / exit holes in the case. 
Bushes should be used to protect cable sheaths from chafing. Ensure that these bushes are correctly sized 
(i.e. close fitting with respect to cable sizing). Note that the bushes should meet a minimum flammability 
specification of UL94 HB. 

4)

 

All cabling should be securely fastened in position using a cable tie through the saddles provided. 

 

Mounting – E box – 17 or 18 Ah  

5)

 

The E box is designed to support two 17 or 18 Ah batteries and as such weighs a total of 19.5 Kg when 
loaded. Ensure that wall fixings are appropriate to support this weight.  

6)

 

The product should be mounted no further than 10 cm from the control and indicating equipment, close 
coupled by conduit if it is being used to power the CIE directly. 

7)

 

Fix to wall or other support structure in correct orientation i.e. with hinge on left hand side, using screws 
of sufficient size and length through the mounting holes. 

8)

 

Protect the battery terminals from any metal surfaces during installation as shorting of the terminals is 
extremely hazardous. 

9)

 

Knock-outs are provided in the case for mating with external trunking or conduit. 

10)

 

Ensure that all unused holes (on the rear of the case) are sealed to prevent the ingress of damp and dust. 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 1 – E Box and Battery mounting

 

 
Mounting – BATT- BOX – 65 Ah 

11)

 

The Battery box is used for 65 Ah batteries is designed to be floor mounted. DO NOT suspend from a wall.   

12)

 

It is important that the battery box and the PSU are co-located as shown, and connected using the 
provided extended 3 metre cable. 

13)

 

A fixing bracket is provided to secure the Battery Box to the wall to prevent it moving away from the wall.  

Summary of Contents for BATT-BOX-65

Page 1: ...volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fau...

Page 2: ...A 7 5 A 10 0 A 7 2 A 6 5 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12 V PS12170 NP17 12 BS131N 2 x 38 Ah 12 V PS12380 NP38 12 2 x 65 Ah 12 V PS12650 NP65 12 BS13...

Page 3: ...N Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN...

Page 4: ...e monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detecte...

Page 5: ...signed to support two 17 or 18 Ah batteries and as such weighs a total of 19 5 Kg when loaded Ensure that wall fixings are appropriate to support this weight 6 The product should be mounted no further...

Page 6: ...ed by conduit if it is being used to power the CIE directly 16 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through...

Page 7: ...ling 4 Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault monitoring is required Figure 4 Power Load and Battery connections 5 Connect the load output...

Page 8: ...4 5 14 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 5 15 If the batteries are housed remotely replace the battery lead assembly including battery te...

Page 9: ...arts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation...

Page 10: ...sposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal rou...

Reviews: