ONNECTIONS

 

 

 

Load + / -- 

Screw terminals Voltage output to load  

GEN PSU Fault  (normally 
closed contact) 

0.10 A @ 60 V dc 16Ω solid state relay contacts, volt free 
Open if Mains failed and battery voltage < 23V or fault PSU fault 
condition, (see below) 

EPS Fault  (normally closed 
contact) 

0.10 A @ 60 V dc 16Ω solid state relay contacts, volt free 
Open if loss of mains for > 10 seconds 

Temperature sensor 

Thermistor input from supplied battery terminal thermistor. 

BATT + / - 

Connection to back up battery using supplied battery lead 

FAN +/ - 

Not used  

RS232 serial interface 

4 pin header   

 

S

IGNALLING AND 

D

IAGNOSTICS

 

 

 
Fault Outputs 

EPS Fault 

GEN Fault 

Condition 

Possible Cause 

Action 

C

LOSED

 

C

LOSED

 

Normal 

operation 

Mains present 
Battery healthy 

None 

O

PEN

 

C

LOSED

 

Standby 

Mode 

Mains lost 
Battery driving load 

Investigate loss of mains 

C

LOSED

 

O

PEN

 

Fault 

Present 

Blown fuses 
Battery fault 
Overload 
Internal fault 

Investigate fault source 
using diagnostic LED 
Rectify fault where 
possible 

O

PEN

 

O

PEN

 

PSU 

Shutdown 

Mains lost 
Standby battery exhausted 

Restore mains as soon 
as possible 

 
LED Indication 

YELLOW LED  

Fault LED 

GREEN LED 

Mains supply On 

DIAGNOSTICS 

Diagnostic LED (Not visible through front panel) 

 
Fault Diagnostic table – Front panel - User 

Yellow LED 

Fault 

Green LED 

Mains 

Condition 

Possible Cause 

Action 

O

FF

 

O

N

 

Normal 

operation 

Mains present 
Battery healthy 

None 

F

LASH 

C

ONTINUOUS

 

O

or

 

O

FF

 

Fault 

Blown fuses 
Battery fault 
Overload 
Internal fault 

Contact service 
engineer 

1

 

P

ULSE

 

O

FF

 

Standby Mode 

Mains lost 
Battery driving load 

Investigate loss of 
mains 

 

Summary of Contents for BATT-BOX-65

Page 1: ...volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fau...

Page 2: ...A 7 5 A 10 0 A 7 2 A 6 5 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12 V PS12170 NP17 12 BS131N 2 x 38 Ah 12 V PS12380 NP38 12 2 x 65 Ah 12 V PS12650 NP65 12 BS13...

Page 3: ...N Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN...

Page 4: ...e monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detecte...

Page 5: ...signed to support two 17 or 18 Ah batteries and as such weighs a total of 19 5 Kg when loaded Ensure that wall fixings are appropriate to support this weight 6 The product should be mounted no further...

Page 6: ...ed by conduit if it is being used to power the CIE directly 16 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through...

Page 7: ...ling 4 Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault monitoring is required Figure 4 Power Load and Battery connections 5 Connect the load output...

Page 8: ...4 5 14 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 5 15 If the batteries are housed remotely replace the battery lead assembly including battery te...

Page 9: ...arts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation...

Page 10: ...sposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal rou...

Reviews: