19
Nozzles
• Ensure there is a gasket inside the nozzle swivel.
• Hand tighten the nozzle onto the monitor discharge.
• Loosen the swivel to reposition the nozzle as shown.
• Tighten the nozzle swivel with a spanner wrench.
• Supply power to the nozzle by connecting the monitor and nozzle harness connectors.
Deutsch
Connector
Gasket Location
Installation Step 2: Configure the EXM2 System
NOTE
: EXM2 systems consisting of a monitor and one Panel Mount or Joystick, a handheld with
gateway, a position display, and an E14x or E16X actuated valve do not require configuration.
EXM2 monitors come factory set for CAN termination and must be at the extreme end of the
main CAN line. See options for CAN wiring and termination on page 15.
The following is a list of reasons why a system would require configuration via Wi-Fi:
• Need maximum travel limits to be different than factory setting
• Reversing monitor controls
• Setting priority or controller for override by primary, secondary, or number
• Reversing valve operation when using an EBXJ valve
• Group number used for multiple monitors on system
• Valve ID change for multiple valves
• CAN address for special system of not using Elkhart Brass controls
• Valve closure before stowing monitor need to be turned off
If the system requires configuration, please refer to the EXM2 System Configuration Manual
(P/N 98612001) for configuration instructions. You can find the most current manual at