Televis
Go
Page 21/68
5.2.4 NAMING NETWORK DEVICES FROM FILE
Network devices can be named by applying the settings in a specific xml file generated by the Offline Configurator application (see
the associated manual).
Go to:
Settings
Interfaces
Device Template
LAN Adapter
Interface
ID
Devices
Address
0
192.168.0.1
15
Name
0.02:00 ID 974LX
0.02:01 ID 974LX
Compact
999
1
999.14:14 TelevisCompact
Legend
Filter devices
Description
Filter resources
Analogue inputs
Digital Inputs
States
Alarms
Show helpers
Show table header
Legend
Select devices
Select a device template
Browse...
Execute
(.xml)
File to be loaded
Device template
Select all
Deselect all
Expand all
Collapse all
Cancel filters
Apply
The page is very similar to the one in
Naming Network Devices Manually or From File, as regards both the device and associated
functions
(for the meaning of many controls).
The file and settings to be applied can be selected in the
File to load (A)
box.
Clicking
Run
will load the template and make it available in the drop-down menu
(D).
Clicking the
Apply (C)
button will apply the current template settings
(D)
to all network devices selected via the check box to the
left of the name (
B
).
The following buttons are presented at the top:
•
Select All
: to select all devices in the list.
•
Deselect All
: to deselect all devices in the list.
•
Expand All
: to view all devices in the interface.
•
Collapse All
: to hide all devices in the interface.
•
Cancel Filters
: to cancel all filters applied.
5.2.5 SETTING THE DATA LOGGING INTERVAL
A data logging interval must be set. The time set (in minutes) is the interval (sample) in which data from the selected resource will be
logged.
Data on
Statuses
,
Alarms
and
Digital Inputs
is not logged in this interval. In these cases, data is recorded when these parameters
change and not over a set interval. To set the interval, go to:
Settings
Data Archive
Control
To access this section, data logging must be suspended (see
Data Logging
section).
On opening this menu, click “
Saved data-logging interval in archive
”, then click the
icon or
Edit
, enter the number
(hours:minutes:seconds) and click the
icon or
Save
.
For expert USERS
: in
Settings
Data Archive
Manage
the “
Maximum Capacity
” (
CM
) (maximum memory used to save data) is set at
7GB
; users can also set the “
part of data
archive to be used for circularity
” (
%CA
) (percentage of memory freed when oldest data is deleted each time the
memory reaches full capacity).
The factory-set value is:
%CA
= 12%.
If you change page without saving, any changes made will be lost (the same as clicking Cancel).
The device will now show the summary in:
Settings
Data archive
Summary
Summary of Contents for TelevisGo
Page 4: ......