VAL PAR AdDRESS
DATA SIZE
Value
Content of register
8806
8806
8806
8806
WORD
WORD
WORD
WORD
1350
1350
1350
1350
1350
1350
1350
1350
(0000010101000110)
(0000010101000110)
(0000010101000110)
(0000010101000110)
8806
8806
8806
8806
Byte
Byte
Byte
Byte
70
70
70
70
1350
1350
1350
1350
(00000101
(00000101
(00000101
(00000101
01000110
))))
8806,8
8806,8
8806,8
8806,8
Byte
Byte
Byte
Byte
5
5
5
5
1350
1350
1350
1350
((((
00000101
01000110)
01000110)
01000110)
01000110)
8806,14
8806,14
8806,14
8806,14
1
1
1
1 bit
bit
bit
bit
0
0
0
0
1350
1350
1350
1350
(0
(0
(0
(0
0
00010101000110)
00010101000110)
00010101000110)
00010101000110)
8806,7
8806,7
8806,7
8806,7
4
4
4
4 bit
bit
bit
bit
10
10
10
10
1350
1350
1350
1350
(00000
(00000
(00000
(00000
1010
1000110)
1000110)
1000110)
1000110)
17.13
17.13
17.13
17.13 Parameters/Client
Parameters/Client
Parameters/Client
Parameters/Client Table
Table
Table
Table
The tables below contain
•
•
A summary description of
parameters
listed with
range
,
default
and unit of measure
All information required to read, write and decode all accessible resources in the controller via Param Manager
and/or Modbus.
There are three tables:
•
The ‘Reference Guide’ indicates visibility at USr/Ins level by
folder
/parameter type and model
•
The
parameters
parameters
parameters
parameters
table
contains all device configuration
parameters
stored in the instrument's non-volatile memory
•
the
Client
Client
Client
Client Table
Table
Table
Table
includes all I/O and alarm state resources available in the instrument's volatile memory.
Description
Description
Description
Description of
of
of
of columns:
columns:
columns:
columns:
FOLDER
FOLDER
FOLDER
FOLDER
MENU
MENU
MENU
MENU
ID
ID
ID
ID
LABEL
LABEL
LABEL
LABEL
This indicates the
label
of the
folder
containing the parameter in question:
see
see
see
see Reference
Reference
Reference
Reference Guide
Guide
Guide
Guide
Indicates the
menu
containing the parameter concerned
•
USr/InS -> indicates that the visible both in the User and Installer menus
•
InS
InS
InS
InS
(in
bold
bold
bold
bold
) -> indicates that the parameter is visible in the installer
menu
only
Indicates the unique index or
ID
with which
the
the
the
the
parameters
parameters
parameters
parameters
are displayed in the instrument’s
menu
.
See
See
See
See parameter
parameter
parameter
parameter
display
display
display
display example
example
example
example
....
This indicates the
label
used to
display
the
parameters
parameters
parameters
parameters
in the instrument's
menu
.
See
See
See
See parameter
parameter
parameter
parameter
display
display
display
display example
example
example
example
....
Parameter
Parameter
Parameter
Parameter
display
display
display
display example
example
example
example
....
Compressors
Compressors
Compressors
Compressors
1002: DIF
Differential
2.0°C
1/14
1/14
1/14
1/14
VALUE
VALUE
VALUE
VALUE PAR
PAR
PAR
PAR
AdDRESS
AdDRESS
AdDRESS
AdDRESS
WHEN UTILIZING MODBUS PROTOCOL ONLY
The whole part represents the address of the MODBUS register containing the value of the resource to be read or written
in the
instrument. The value after the point indicates the position of the most significant data bit in the register; if not indicated
it is taken to be zero. This information is always provided when the register contains more than one information item, and
it is necessary to distinguish which bits actually represent the data (the working size of the data indicated in the column
DATA SIZE
is also taken into consideration) Given that the modbus registers have the size of one WORD (16 bit), the index
number after the point can vary from 0 (least significant bit -LSb-) to 15 (most significant bit -MSb-)
Examples (in binary form the least significant bit is the first on the right):
Important: when the register contains more than one data item, during the write operation proceed as follows:
•
•
•
read current register value
modify the bits that represent the resource concerned
write the register
VIS
VIS
VIS
VIS PAR
PAR
PAR
PAR ADDRESS
ADDRESS
ADDRESS
ADDRESS
WHEN UTILIZING MODBUS AND PARAM MANAGER PROTOCOL
Same as above. In this case, the parameter visibility value is in the MODBUS register address.
By
default
, all
parameters
have:
•
•
•
DATA SIZE
Range
U.M.
2 bit
0…3
number
•
Visibility
Visibility
Visibility
Visibility
0
0
0
0…
…
…
…3
3
3
3
o
0 = parameter not visible
EWHT 1800LX
78/141
Summary of Contents for EWHT 1800LX
Page 100: ...EWHT 1800LX 100 141 ...
Page 124: ...EWHT 1800LX 124 141 ...
Page 137: ...EWHT 1800LX 137 141 ...
Page 138: ...EWHT 1800LX 138 141 ...