background image

PAR.

DESCRIPTION

RANGE

DEFAULT

VALUE

LEVEL

U.M.

SEt

Set point with range falling between the minimum 
LSE set point and the maximum HSE set point. The 
value of the set point is in the 

machine status 

menu

LSE...HSE

0.0

°C/°F

diF

When the compressor stops when it reaches the
set point value, it restarts at a value corresponding
to the set point plus the value of the differential It
must not be 0

0.1...30.0

2.0

1-2

°C/°F

HSE

Maximum set point value

LSE...302

50.0

1-2

°C/°F

LSE

Minimum set point value

-58.0...HSE

-50.0

1-2

°C/°F

OSP

Offset point. Value to be added to set point if
reduced set point is activated Economy function).

-30.0...30.0

0

2

°C/°F

Cit

Minimum compressor ON time. Minimum time for 
activating a compressor before deactivation Not
active if=0

0...250

0

2

min

CAt

Maximum compressor ON time. Maximum time for
activating a compressor before deactivation Not
active if=0

0...250

0

2

min

Ont   (1)

Compressor activation time if probe is faulty. If set
to 1 with OFt=0 the compressor always remains on
whereas if OFt>0 it operates in duty cycle mode
(see 

Duty Cycle 

diagram)

0...250

0

1-2

min

OFt   (1)

Compressor shut-down time if probe is faulty. If set
to 1 with Ont=0 the compressor always remains off
whereas if OFt>0 it operates in duty cycle mode
(see 

Duty Cycle 

diagram)

0...250

1

1-2

min

dOn

Delay in activating compressor relay after start-up

0...250

0

1-2

sec

dOF

Delay after shut-down; between compressor relay
shut-down and subsequent start-up the specified
time must elapse.

0...250

0

1-2

min

dbi

Delay between switch-ons; the specified time must
elapse between two subsequent switch-ons

0...250

0

1-2

min

OdO 

Delay in activating outputs after start-up of instru-
ment or after a power failure. Not active if=0

0...250

0

1-2

min

dty

Defrost type:
0 = Electrical or Off Cycle defrost (Compressor 
OFF during Defrost;
1 = Reverse cycle defrost (hot gas - Compressor 
On during Defrost);
2 = ’Free’ : Independent defrost (compressor cycles ON/OFF according to temperature during defrost)

0/1/2

0

1-2

flag

dit

Period of time elapsing between the start of two
defrosts 0=function disabled

0...250

6

1-2

hours

dt1

Unit of measurement for defrost times (par. dit)
0=”dit” expressed in hours 
1=”dit” expressed in minutes 
2=”dit” expressed in seconds

0/1/2

0

2

flag

NOTE:   At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the 

level 2 parameters. The symbol 1-2 indicates the parameters that are displayed at both menu levels

Defrosting controller

-dEF label

Compressor controller

-CP label

dt2

Unit of measurement for duration of defrosting
(dEt parameter) 
0= “dEt” parameter expressed in hours 
1= “dEt” parameter expressed in minutes 
2= “dEt” parameter expressed in seconds

0/1/2

1

2

flag

dCt

Selection of defrosting time count mode. 
0=compressor operating hours DIGIFROST®
method). Defrosting active only if compressor is
on. 
1 = equipment operating hours; defrost counting is
always active when the machine is on 
2=compressor stop Each time the compressor stops
a defrosting cycle according to par. dtY 
3=con RTC. Defrosting at times set by dE1...dE8,
F1...F8 parameters.

0/1/2/3

1

1-2

flag

dOH 

Delay between start of first defrosting operation
and start-up of instrument.

0...59

0

1-2

min

dEt

Defrosting time-out; determines maximum dura-
tion of defrosting.

1...250

30

1-2

min

dE2

Defrosting time-out on second evaporator; deter-
mines maximum duration of defrosting on 2nd
evaporator

1...250

30

2

min

EWDR 983-985/CS (LX) - EWDR 985/CSK (LX)

4/12

Summary of Contents for EWDR 983/CS

Page 1: ... main menu level The set point setting folder is also closed when the time out elapses Alarm on If an alarm condition exists when the Machine Status menu is accessed the ALfolder label appears Real Time Clock C models By pressing the set button when the rtc label appears the label d00 days is displayed Use the UP and DOWN buttons to set days If you do not use the buttons for over 2 seconds or if y...

Page 2: ...input NOTE the sign indicates that the input is activated when the contact is closed The sign indicates that the input is activated when the contact is open LIGHT CONTROLLER Controls the light relay The function can be started in two different ways If you press the light button the light relay is switched on if it was off and is switched off if it was on The light status is recorded by the device ...

Page 3: ...ntil the door is closed MECHANICAL ASSEMBLY The EWDR 983 985 CS LX EWDR 985 CSK LX is designed to be wall mounted removable brackets or mounted on DIN rail Omega 3 The unit operates correctly with an ambient temperature range of between 5 and 55 C Units must not be installed in excessively humid and or dirty loca tions ELECTRICAL CONNECTIONS Warning Always switch off machine before working on elec...

Page 4: ...ing outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Defrost type 0 Electrical or Off Cycle defrost Compressor OFF during Defrost 1 Reverse cycle defrost hot gas Compressor On during Defrost 2 Free Independent defrost compressor cycles ON OFF according to temperature during defrost 0 1 2 0 1 2 flag dit Period of time elapsing between the start of t...

Page 5: ...C F Fdt Delay before fan activation after defrosting 0 250 0 1 2 min dt Dripping time 0 250 0 1 2 min FCO Disables fans with compressor off Off y fans active with thermostat in response to value read by defrost probe see FSt parameter n fans off dc duty cycle using parameters Fon and FoF n y dc y 1 2 flag dFd Disables evaporator fans y fans disabled n fans enabled y n y 1 2 flag Fod Enables fan st...

Page 6: ... label E00 Functions enabled during events 0 control disabled 1 reduced set point 2 reduced set point light 3 reduced set point light aux 4 instrument off 0 4 0 1 2 num E01 Hours minutes of start of intervention Starting from this time the NIGHT mode will be enabled The duration is determined by EO2 0 23 0 59 0 1 2 hours min E02 Duration of event Sets the duration of the event that begins at time ...

Page 7: ...ayed 55 0 140 50 0 2 C F HdL Maximum value that can be displayed 55 0 302 140 0 2 C F ddL display during defrosting 0 displays temperature read by thermostat control probe 1 displays temperature read entering defrost cycle until set point is reached 2 displays dEF label during defrosting until set point is reached or when Ldd expires 0 1 2 1 1 2 flag Ldd Time out for unlocking display with ddL 2 i...

Page 8: ... 1st evaporator dSt temperature 2nd evaporator dS2 2 defrosting activated if both conditions are met temperature 1st evaporator dSt temperature 2nd evaporator dS2 0 1 2 1 2 num PA2 in the CnF folder when you enter the correct password you can access level 2 parameters from label PA2 by pressing the set button rEL Device version Read only parameter 0 1999 1 tAb Parameter table Reserved Read only pa...

Page 9: ... days set minutes if present d00 Sunday d2 Ed change value E00 03 press and release single press d3 d1 E01 E00 E02 set E01 set E00 set E02 nad E03 set E03 as above as above as above day 1 Sunday day 2 Monday day 3 Tuesday Every Day all days FnC FUNCTION FOLDER The FnC folder last folder visible from the Programming Menu level 1 contains the following functions They are activated using the set butt...

Page 10: ...nt HAL AFd 2 Setpoint LAL AFd Setpoint HAL AFd Setpoint Temperature lower than or equal to LAL LAL with sign Temperature lower than or equal to Set point LAL Temperature greater than or equal to Setpoint HAL Temperature greater than or equal to HAL HAL with sign Maximum temperature alarm release Minimum temperature alarm release Temperature higher than or equal to LAL AFd Temperature greater than ...

Page 11: ... programmed for Duty Cycle Ont OFt Compressor output 0 0 OFF 0 0 OFF 0 0 ON 0 0 dc OUT On Off OFt Ont Ont The error condition for probe 1 compressor causes the following E1 code appears on display the controller is activated as indicated by the Ont and OFt parame ters if programmed for Duty Cycle DUTY CYCLE DIAGRAM The technical characteristics in this document concerning measurements range accura...

Page 12: ...e between the first and last instrument in the network must be approximately 50m NOTE the serial link between the devices is powered Master Instrument that controls the networks and sends commands to the Slaves The Master is selected using parameter L00 the value 0 defines the Master Slave Instrument s with own controllers that also perform s commands issued by the Master with parameters L03 L06 D...

Reviews: