MINIMUM AND MAXIMUM TEMPERA-
TURE ALARM

If an alarm condition occurs and alarm
exclusion times are not in progress (see
alarm exclusion parameters), the alarm
icon lights up permanently and the relay
that is configured as an alarm is activated.
This type of alarm does not affect the reg-
ulating in progress. 
Alarms are considered as absolute
(default) values or as values related to the
Set point (the distance from the Set point
itself) and based on the Att parameter. 
If the alarms are relative (Att=1), the para-
meter HA1 is set to positive values and
LA1 to negative values.
This alarm condition can be viewed in the
folder “AL” with labels “AH1-AL1”. 

CLOCK BATTERY ALARM

This alarm is activated in the following
situations:
- when the instrument is switched on for
the first time and the clock is set
- when the instrument is switched on
again after a power off lasting more than
24/32 hours. 
The alarm will stop as soon as the
day/hour/minutes are set using the set
parameters. 
Resetting is automatic and there is no
need to restart the instrument.

ALARM WITH THRESHOLD REFERRING
TO PROBE 3

An alarm is associated with probe 3 that
refers to a threshold that is reset at a
specified differential. 
By setting parameter PbA=3 probe 3 will
signal a high or low temperature alarm
for exceeding the set value. 
The alarm is handled in the same way as
the other temperature alarms and stan-
dard signal delays are used.

DEFROST ALARM

If defrosting does not reach the end of
cycle temperature but is terminated by a
time out, the alarm controller is immedi-
ately activated. 
An alarm LED remains on and the alarm
is recorded in the Ad2 label alarm menu. 
The alarm is automatically reset as soon
as the next defrost cycle starts. The
alarm LED can only be manually
switched off with a silencing procedure.

EXTERNAL ALARM

It is set if the digital input is enabled
with the delay specified by parameter
dAd and remains enabled until the next
time the digital input is deactivated. 
The alarm consists of an alarm LED that
remains on, activation of a buzzer and
deactivation of all the device loads (if
specified by the EAL parameter). 
If an external alarm is present the EA
label is displayed in the AL folder. 
It is reset the next time the digital input
is deactivated and the buzzer can be
manually silenced.

OPEN DOOR ALARM

This alarm is generated when the door is
open for longer than the value specified
in parameter tdO. 

door open alarm is signalled in the

alarm folder (AL) and the LED and alarm
relay are switched on. 
The OPd label is also displayed. 
The relay can be deactivated by pressing
the silencing button. The LED continues
to flash intermittently and the OPd label
remains in the alarm menu until the
door is closed.

MECHANICAL ASSEMBLY

The 

EWDR 983-985/CS (LX) - EWDR

985/CSK (LX)

is designed to be wall-

mounted (removable brackets) or
mounted on DIN rail (Omega 3). 
The unit operates correctly with an
ambient temperature range of between 
-5 and 55 °C. Units must not be installed
in excessively humid and/or dirty loca-
tions.

ELECTRICAL 
CONNECTIONS

Warning! Always switch off machine
before working on electrical 
connections.

The instrument has screw terminal blocks
for connecting cables with a maximum
diameter of 2.5 mm

2

(only one conductor

per terminal block for power 
connections): for terminal capacity, see
the label on the instrument. 
The relay outputs are voltage free. 
Do not exceed the maximum current
allowed. For higher loads, use a suitable
contactor. 
Make sure that the power voltage com-
plies with the device voltage. 
Probes have no connection polarity and
can be extended using an ordinary bipo-
lar cable (note that if probes are extend-
ed this affects the electromagnetic com-
patibility (EMC) of the instrument: special
care must be used when wiring). 
The RS-485 serial and TTL serial cables
must be kept separate from the power
cables.

TECHNICAL DATA

Casing: plastic 4 Din modules
Dimensions: front 70x85 mm, depth
61mm.                             
Mounting: on DIN rail (Omega 3) or
wall-mounted.
Connections: on screw terminal block for

2.5mm

2

conductors

(only one conductor per terminal block
for power connections)
Operating temperature: -5...55°C. 
Storage temperature: -30...85°C.
Operating and storage ambient humidity:
10...90 % RH (non-condensing).
Display: 3 sign 
Analogue inputs: 3 NTC/PTC inputs
(parameter configurable)           
Digital inputs: 2 voltage-free parameter-
configurable digital inputs.      
Serial: 

-TTL for Copy Card
-RS485 for connection to Televis

System

(for /CS LX - /CSK LX models only) 

Digital outputs:                                    

EWDR 983 (/CS LX):

2 digital outputs on relay:8A 1/2hp 250V
SPDT; 16A 1hp 250V SPDT;

EWDR 985 (/CS LX):

4 digital outputs on relays: 8A 1/2hp
250V SPST; 8A 1/2hp 250V SPDT; 16A
1hp 250V SPST; 8A 1/2hp 250V SPST.
Configurable 12V

c

/24mA output 

EWDR 985/CSK (LX):

4 digital outputs on relays: 8A 1/2hp
250V SPST; 8A 1/2hp 250V SPDT; 16A
1hp 250V SPST; 8A 1/2hp 250V SPST.        
Link: Output for Link network

Resolution: 1 or 0.1°C. 
Accuracy: better than 0.5% of bottom
scale +1 digit 
Consumption: 5VA 
Power supply: 230V

a

EWDR 983-985/CS (LX) - EWDR 985/CSK (LX)

3/12

DISPLAY

AH1

AL1

AH3

AL3

Ad2 
EA 
Opd
E7*

Press any button to silence the alarm. The LED will
start to blink. If simultaneous, they will be showed
on the display alternately every 2 seconds

*ONLY FOR EWDR 985/CSK (LX)
In the event of addressing errors, E7 will not be
shown, but the  display will blink.

ALARM

High temperature alarm (referring to
room probe or probe 1) 
Low temperature alarm (referring to
room probe or probe 1) 
High temperature alarm (referring to
probe 3) 
Low temperature alarm (referring to
probe 3) 
Defrosting timed out 
External alarm 
Door Open Alarm 
Master-Slave Communication failure

Summary of Contents for EWDR 983/CS

Page 1: ... main menu level The set point setting folder is also closed when the time out elapses Alarm on If an alarm condition exists when the Machine Status menu is accessed the ALfolder label appears Real Time Clock C models By pressing the set button when the rtc label appears the label d00 days is displayed Use the UP and DOWN buttons to set days If you do not use the buttons for over 2 seconds or if y...

Page 2: ...input NOTE the sign indicates that the input is activated when the contact is closed The sign indicates that the input is activated when the contact is open LIGHT CONTROLLER Controls the light relay The function can be started in two different ways If you press the light button the light relay is switched on if it was off and is switched off if it was on The light status is recorded by the device ...

Page 3: ...ntil the door is closed MECHANICAL ASSEMBLY The EWDR 983 985 CS LX EWDR 985 CSK LX is designed to be wall mounted removable brackets or mounted on DIN rail Omega 3 The unit operates correctly with an ambient temperature range of between 5 and 55 C Units must not be installed in excessively humid and or dirty loca tions ELECTRICAL CONNECTIONS Warning Always switch off machine before working on elec...

Page 4: ...ing outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Defrost type 0 Electrical or Off Cycle defrost Compressor OFF during Defrost 1 Reverse cycle defrost hot gas Compressor On during Defrost 2 Free Independent defrost compressor cycles ON OFF according to temperature during defrost 0 1 2 0 1 2 flag dit Period of time elapsing between the start of t...

Page 5: ...C F Fdt Delay before fan activation after defrosting 0 250 0 1 2 min dt Dripping time 0 250 0 1 2 min FCO Disables fans with compressor off Off y fans active with thermostat in response to value read by defrost probe see FSt parameter n fans off dc duty cycle using parameters Fon and FoF n y dc y 1 2 flag dFd Disables evaporator fans y fans disabled n fans enabled y n y 1 2 flag Fod Enables fan st...

Page 6: ... label E00 Functions enabled during events 0 control disabled 1 reduced set point 2 reduced set point light 3 reduced set point light aux 4 instrument off 0 4 0 1 2 num E01 Hours minutes of start of intervention Starting from this time the NIGHT mode will be enabled The duration is determined by EO2 0 23 0 59 0 1 2 hours min E02 Duration of event Sets the duration of the event that begins at time ...

Page 7: ...ayed 55 0 140 50 0 2 C F HdL Maximum value that can be displayed 55 0 302 140 0 2 C F ddL display during defrosting 0 displays temperature read by thermostat control probe 1 displays temperature read entering defrost cycle until set point is reached 2 displays dEF label during defrosting until set point is reached or when Ldd expires 0 1 2 1 1 2 flag Ldd Time out for unlocking display with ddL 2 i...

Page 8: ... 1st evaporator dSt temperature 2nd evaporator dS2 2 defrosting activated if both conditions are met temperature 1st evaporator dSt temperature 2nd evaporator dS2 0 1 2 1 2 num PA2 in the CnF folder when you enter the correct password you can access level 2 parameters from label PA2 by pressing the set button rEL Device version Read only parameter 0 1999 1 tAb Parameter table Reserved Read only pa...

Page 9: ... days set minutes if present d00 Sunday d2 Ed change value E00 03 press and release single press d3 d1 E01 E00 E02 set E01 set E00 set E02 nad E03 set E03 as above as above as above day 1 Sunday day 2 Monday day 3 Tuesday Every Day all days FnC FUNCTION FOLDER The FnC folder last folder visible from the Programming Menu level 1 contains the following functions They are activated using the set butt...

Page 10: ...nt HAL AFd 2 Setpoint LAL AFd Setpoint HAL AFd Setpoint Temperature lower than or equal to LAL LAL with sign Temperature lower than or equal to Set point LAL Temperature greater than or equal to Setpoint HAL Temperature greater than or equal to HAL HAL with sign Maximum temperature alarm release Minimum temperature alarm release Temperature higher than or equal to LAL AFd Temperature greater than ...

Page 11: ... programmed for Duty Cycle Ont OFt Compressor output 0 0 OFF 0 0 OFF 0 0 ON 0 0 dc OUT On Off OFt Ont Ont The error condition for probe 1 compressor causes the following E1 code appears on display the controller is activated as indicated by the Ont and OFt parame ters if programmed for Duty Cycle DUTY CYCLE DIAGRAM The technical characteristics in this document concerning measurements range accura...

Page 12: ...e between the first and last instrument in the network must be approximately 50m NOTE the serial link between the devices is powered Master Instrument that controls the networks and sends commands to the Slaves The Master is selected using parameter L00 the value 0 defines the Master Slave Instrument s with own controllers that also perform s commands issued by the Master with parameters L03 L06 D...

Reviews: