PAR.

DESCRIPTION

RANGE

DEFAULT

VALUE*

LEVEL**

U.M.

dSt

End of defrost temperature (determined by evapo-
rator probe)

-50.0...150

8.0

1-2

°C/°F

dS2

End of defrost temperature (determined from
probe on 2nd evaporator)

-50.0...150

8.0

2

°C/°F

dPO

Determines when instrument starts up if the
defrosting cycle must be activated (if the tempera-
ture on the evaporator allows this) y=defrosting
activated at start-up n=defrosting not activated at
start-up

n/y

n

1-2

flag

tcd

minimum time for each compressor state before
defrosting “Ontime if >0; “Offtime if >0

-31...31

0

2

min

Cod

Compressor “Off” time before defrost cycle. The
compressor is not turned on if a defrost cycle is
expected in the time indicated by the parameter.
0=Function excluded

0...60

0

2

min

F

an controller

-F

An label

Defrosting controller

-dEF label

FPt

Determines if “FSt” and “Fot” are expressed as
absolute values or in relation to set point
0=absolute value; 1=value related to set point

0/1

0

2

flag

FSt

Fan stop temperature. Temperature limit that, if
exceeded by the value read by the evaporator
probe, stops the fans.

-50.0...150.0

2.0

1-2

°C/°F

Fot

Fan start temperature. If the temperature read by
the evaporator probe is lower than the set value
the fans remain off.

-50.0...150.0

-50.0

2

°C/°F

NOTE:   At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the 

level 2 parameters. The symbol 1-2 indicates the parameters that are displayed at both menu levels

FAd

Fan activation intervention differential. (see “FSt”,
“Fot”)

1.0...50.0

2.0

1-2

°C/°F

Fdt

Delay before fan activation after defrosting

0...250

0

1-2

min

dt

Dripping time

0...250

0

1-2

min

FCO

Disables fans with compressor off (Off) 
y = fans active (with thermostat; in response to
value read by defrost probe, see “FSt” parameter);
n = fans off; 
dc = duty cycle (using parameters “Fon” and “FoF”)

n/y/dc

y

1-2

flag

dFd

Disables evaporator fans. y=fans disabled n=fans
enabled

y/n

y

1-2

flag

Fod

Enables fan stop with door open and fan re-start
when door is closed (if fans were on). 
n=fans stop; 
y=fans unchanged

n/y

n

2

flag

FdC

Fan shut-down delay after compressor stop
0=function excluded

0...99

0

2

min

Fon

Fan start-up time in Duty Cycle mode; valid for
FCO=dc and H42=1 (presence of probe 2)

0...99

0

2

min

FoF

Fan shut-down time in Duty Cycle mode; valid for
FCO=dc and H42=1 (presence of probe 2)

0...99

0

2

min

Alarms-AL label

Att

Determines if “LAL” and “HAL” are expressed as
absolute values or as a differential related to the
set point 
0=absolute value 
1=value related to set point

0/1

0

2

flag

AFd

Alarm differential

1.0...50.0

2.0

1-2

°C/°F

HAL   (4)

Maximum alarm. Temperature limit (whose
absolute or relative value status is regulated by
“Att”) above which the alarm is activated.

LAL...150.0

50.0

1-2

°C/°F

LAL   (4)

Minimum alarm. Temperature limit (whose
absolute or relative value status is regulated by
“Att”) below which the alarm is activated.

-50.0...HAL

-50.0

1-2

°C/°F

PAO  (5)

Alarm exclusion time after start-up of instrument
following a power failure

0...10

0

1-2

hours

dAO

Alarm exclusion time after defrosting

0...999

0

1-2

min

“dd (2)

dE1...dE8; daily defrost start time

ONLY VISIBLE WHEN dCt=3

0...23/0...59

24

1-2

hours/min

“Fd (2)

F1...F8 festive defrost start time

ONLY VISIBLE WHEN dCt=3

0...23/0...59

24

1-2

hours/min

EWDR 983-985/CS (LX) - EWDR 985/CSK (LX)

5/12

Summary of Contents for EWDR 983/CS

Page 1: ... main menu level The set point setting folder is also closed when the time out elapses Alarm on If an alarm condition exists when the Machine Status menu is accessed the ALfolder label appears Real Time Clock C models By pressing the set button when the rtc label appears the label d00 days is displayed Use the UP and DOWN buttons to set days If you do not use the buttons for over 2 seconds or if y...

Page 2: ...input NOTE the sign indicates that the input is activated when the contact is closed The sign indicates that the input is activated when the contact is open LIGHT CONTROLLER Controls the light relay The function can be started in two different ways If you press the light button the light relay is switched on if it was off and is switched off if it was on The light status is recorded by the device ...

Page 3: ...ntil the door is closed MECHANICAL ASSEMBLY The EWDR 983 985 CS LX EWDR 985 CSK LX is designed to be wall mounted removable brackets or mounted on DIN rail Omega 3 The unit operates correctly with an ambient temperature range of between 5 and 55 C Units must not be installed in excessively humid and or dirty loca tions ELECTRICAL CONNECTIONS Warning Always switch off machine before working on elec...

Page 4: ...ing outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Defrost type 0 Electrical or Off Cycle defrost Compressor OFF during Defrost 1 Reverse cycle defrost hot gas Compressor On during Defrost 2 Free Independent defrost compressor cycles ON OFF according to temperature during defrost 0 1 2 0 1 2 flag dit Period of time elapsing between the start of t...

Page 5: ...C F Fdt Delay before fan activation after defrosting 0 250 0 1 2 min dt Dripping time 0 250 0 1 2 min FCO Disables fans with compressor off Off y fans active with thermostat in response to value read by defrost probe see FSt parameter n fans off dc duty cycle using parameters Fon and FoF n y dc y 1 2 flag dFd Disables evaporator fans y fans disabled n fans enabled y n y 1 2 flag Fod Enables fan st...

Page 6: ... label E00 Functions enabled during events 0 control disabled 1 reduced set point 2 reduced set point light 3 reduced set point light aux 4 instrument off 0 4 0 1 2 num E01 Hours minutes of start of intervention Starting from this time the NIGHT mode will be enabled The duration is determined by EO2 0 23 0 59 0 1 2 hours min E02 Duration of event Sets the duration of the event that begins at time ...

Page 7: ...ayed 55 0 140 50 0 2 C F HdL Maximum value that can be displayed 55 0 302 140 0 2 C F ddL display during defrosting 0 displays temperature read by thermostat control probe 1 displays temperature read entering defrost cycle until set point is reached 2 displays dEF label during defrosting until set point is reached or when Ldd expires 0 1 2 1 1 2 flag Ldd Time out for unlocking display with ddL 2 i...

Page 8: ... 1st evaporator dSt temperature 2nd evaporator dS2 2 defrosting activated if both conditions are met temperature 1st evaporator dSt temperature 2nd evaporator dS2 0 1 2 1 2 num PA2 in the CnF folder when you enter the correct password you can access level 2 parameters from label PA2 by pressing the set button rEL Device version Read only parameter 0 1999 1 tAb Parameter table Reserved Read only pa...

Page 9: ... days set minutes if present d00 Sunday d2 Ed change value E00 03 press and release single press d3 d1 E01 E00 E02 set E01 set E00 set E02 nad E03 set E03 as above as above as above day 1 Sunday day 2 Monday day 3 Tuesday Every Day all days FnC FUNCTION FOLDER The FnC folder last folder visible from the Programming Menu level 1 contains the following functions They are activated using the set butt...

Page 10: ...nt HAL AFd 2 Setpoint LAL AFd Setpoint HAL AFd Setpoint Temperature lower than or equal to LAL LAL with sign Temperature lower than or equal to Set point LAL Temperature greater than or equal to Setpoint HAL Temperature greater than or equal to HAL HAL with sign Maximum temperature alarm release Minimum temperature alarm release Temperature higher than or equal to LAL AFd Temperature greater than ...

Page 11: ... programmed for Duty Cycle Ont OFt Compressor output 0 0 OFF 0 0 OFF 0 0 ON 0 0 dc OUT On Off OFt Ont Ont The error condition for probe 1 compressor causes the following E1 code appears on display the controller is activated as indicated by the Ont and OFt parame ters if programmed for Duty Cycle DUTY CYCLE DIAGRAM The technical characteristics in this document concerning measurements range accura...

Page 12: ...e between the first and last instrument in the network must be approximately 50m NOTE the serial link between the devices is powered Master Instrument that controls the networks and sends commands to the Slaves The Master is selected using parameter L00 the value 0 defines the Master Slave Instrument s with own controllers that also perform s commands issued by the Master with parameters L03 L06 D...