Electromagnetic flowmeter FLONET FN50xx.1
ELIS PLZEN a. s., Lucni 425/15, 301 00 Plzen, Czech Republic, Phone: +420/377 517 711, fax: +420/377 517 722
Es90716K
7.2. Pulse output OUT1
In any of the impulse modes, an impulse will be generated as soon as a defined (preset) fluid volume passes
through the meter sensor. Pulse width is fixed at 100 ms. For the duration of the impulse output is closed.
The following table shows the optimal choice of impulse numbers depending on the dimension of the
flowmeter.
Q
max
Pulse
number
DN
l/s
l/pulse
15
1,6
0,1
20
3
0,1
25
5
0,1
32
8,33
0,1
40
12,5
1
50
20
1
65
33,33
1
80
50
1
100
77,77
1
125
119,44
10
150
180,55
10
200
319,4
10
250
500
10
300
700
10
350
972
10
400
1250
100
500
2000
100
600
2778
100
700
3889
100
800
5000
100
7.3. Production data
The production label consist all the parameters that are set at the factory.
Constant K1
Pulse number
Numbers of samples
Suppressed flow
Constant of a sensor K1
– defines a basic calibration factor of a sensor
Pulse number
Numbers of samples
for averaging
– it stabilizes a flow value by flow drifting. It is possible to set it by
production on values 25, 50, 100, 150, 200, 250 of samples.
Suppressed flow
– it defines a flow area (symmetric around zero), where all outputs values are set on zero.