11
INSTALLATION MANUAL
Cover of
non-flammable
material
Air cavity 20mm
Air cavity 50mm
Distance
≥ 100mm
Non-flammable
cover
Wall insulation
Distance to
insulation
≥ 20mm
Non-flammable
insulation plate
Figure 2B: Flammable wall-/ceiling
Construction for a situation with
a flammable wall (U-Value ≥ 0,4Wm
2
/K)
Flammable wall
Non-flammable
floor
Flammable floor
Convection grille
2x 150cm
2
Distance to
convection grille
≥ 200mm
Radiation distance
to flammable
objects ≥ 500mm
Outside gas
fireplace ~200ºC
Distance fireplace to
non-flammable
floor ≥ 100mm
Figure 6-4: Flammable wall-/ceiling
Air cavity 50mm
Air cavity 20mm
Non-flammable
insulation 25mm
Distance to
insulation ≥ 20mm
Figure 2A: Flammable wall-/ceiling
Construction for a situation with
a flammable wall (U-Value ≥ 0,4Wm
2
/K)
False ceiling
Distance ≥ 100mm
Flammable wall
Wall insulation
Insulation plate
Nonflammable
floor
Flammable floor
Covering of
non-flammable
material
Convection grille
2x 150cm
2
Distance to
convection grille
≥ 200mm
Radiation distance
to flammable
objects ≥ 500mm
Outside gas
fireplace ~200ºC
Distance fireplace to
nonflammable
floor ≥ 100mm
Figure 6-3: Non-flammable wall-/ceiling
Assembly regulations
(Figure 6-3 and 6-4)
•
Load-bearing walls and ceilings must be covered in a
protective fire resistant plate.
Never use flammable materials around the fireplace or cove.
The minimal distance between the device and non-flammable
materials must be at 50 mm to ensure a convection air flow.
Make sure there is a good air ventilation in the cove. The
temperature that leaves through the ventilation grilles must not
be higher than 85°C. Therefore one should always make sure
there are enough ventilation grilles in the upper and lower parts
of the cove.
Hot air outlets and ventilation grilles
The ventilation grilles are to be placed at a minimal distance of
20cm from the ceiling and 30cm from any built-in furniture from
the side, any flammable material or load-bearing concrete parts.
To avoid heat accumulation in the cove a non-flammable false
ceiling is to be placed directly above the grilles. The ventilation
grilles need to be easy to clean at all times.
Floor protection
Between the device and the ground a minimal distance of
10cm is to be taken into account. The temperature of the floor
under the device needs be less than 85°C and the floor of the
conversion around the fireplace is to be constructed of non-
flammable materials. If necessary the floor is to be covered with
an insulation layer to protect it from unauthorized temperatures.
Radiation
When the fireplace is turned on, heat radiation will escape
through the ceramic glass and will heat up the environment.
Therefore it is important that a minimal distance between
the ceramic glass and any flammable material in front of the
fireplace is 40cm.
Electrical pipes
The conversion has to be free of the usual electric installation
pipes, if these are not protected against temperatures over
30°C by the necessary precautions. Special pipelines with an
heightened heat resistance are permitted.