Maximum pipe extension, for outside wall.
Use shaded area to calculate maximum
alowable length (H) for the corresponding
pipe rise (V).
0.5
V (METRES)
4.5
5.0
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0
1.0
1.5
2.0
2.5
3.0
H (METRES)
Maximum pipe extension, for outside wall.
Use shaded area to calculate maximum
alowable length (H) for the corresponding
pipe rise (V).
39
VENTING
Element4 Gas Fireplaces
European
Home
.com
3’3”
1.0
m
Vertical
Rise
0”/0
mm
HORIZONTAL TERMINATION GRAPH FOR OPTICA AND BIOPTICA ONLY
1’7”
0.5
m
3’3”
1.0
m
4’11”
1.5
m
6’6”
2.0
m
8’2”
2.5
m
9’10”
3.0
m
11’5”
3.5
m
13’1”
4.0
m
14’9”
4.5
m
16’4”
5.0
m
Horizontal
Run
Graph 2 shows the maximum horizontal vent run (to the outside wall) for a certain vertical vent rise on Optica and Bioptica models
ONLY. The allowable venting configuration MUST be within the shaded area.
• When using a wall-mounted termination a maximum of
2
horizontally-mounted elbows (45° or 90°) may be used.
- For each 45° elbow, 20”/500
mm
must be subtracted from the horizontal length allowance.
- For each 90° elbow, 40”/1000
mm
must be subtracted from the horizontal length allowance.
• Between 3’3”/1.0
m
and 4’11”/1.5
m
of rise, every increase of 1”/25
mm
allows an increased run of 4”/100
mm
.
Example A: With a total rise of 60”/1.52
m
and one horizontal 90° elbow, a total run of 13’1”/4.0
m
is allowed
Example B: If the rise is 3’10”/1168
mm
then the run can be no longer than 12’/3.67
m.
Example C: If the run is 5’ 6”/1.68
m
then the rise must be at least 2’2”/670
mm
.
4’11”
1.5
m
6’6”
2.0
m
8’2”
2.5
m
9’10”
3.0
m
Graph 2
. Horizontal Terminations on Optica and Bioptica models ONLY