0608
23
7
D1083
5 x A
D0460
Notice
Date Page
05102004
INSTALLATION
MANUAL
Connection of the ironer evacuation system
Fresh air inlet
To allow the dryer ironer to work at its best, it
is important that the laundry air inlet passes
through an opening from the outside.
The fresh air arrival must be equivalent to
the volume of evacuated air(please refer to
the output of the fans at zero pressure in the
technical characteristics).
Note :
In the case of several machines,
these values should be added together.
In order to prevent drafts in the room, the
best solution is to place the air inlet behind
the machine.
In the case of a machine with gas heating,
it is essential that the rooms should be
ventilated.
The free section of the air inlet must be
5 times greater than the section of the
evacuation pipe.
Do not forget to allow for the fact that grills
often occupy half the total area of the free
air opening.
Evacuation duct
It is recommended that a separate smooth-walled evacuation duct should be connected to each
dryer, providing the least possible resistance to air.
Check that the shaft flow is at least twice the capacity of the ironer exhaust fan.
It is essential that the diameter of the evacuation pipe should be
selected as a function of each installation so that the pressure
loss never exceed 200 Pa ( 0.029 psi) (value measured at ambient
temperature).
To prevent any risk of burnings, the vapours’ evacuation duct of the
flatwork ironers of the linen has to be temperature insulated (to be
done by the customer).
These conditions are
ABSOLUTELY ESSENTIAL
for correct working of the ironer.
7. Installation